Figure 3 

 

 

GR2675 

 
2.2.4 

For conduit entry or J-Box mounting, remove the 

appropriate threaded plug on the electrical housing 

2.2.5

 Insert the supply wires or thread conduit through 

the hole and secure housing to the wall using fasteners, 
not included, that are appropriate for the size and weight 
of the luminaire as well as the substrate the luminaire is 
being mounted to. 

2.2.6 

Apply a continuous bead rubber silicon to seal the 

back housing to the wall. 

2.2.7 

Apply a continuous bead rubber silicon to fully seal 

any unused conduit entry points. 

 
2.3 Wiring the Luminaire – Standard Luminaire 
2.3.1 

Using the provided chains and hooks, hang the 

heatsink on the electrical housing for temporary support 
during wiring.

  

2.3.2 

Check Voltage to ensure the line voltage matches 

the voltage range shown in the luminaire description on 
the fixture label. 

2.3.3 

Reconnect any wiring that had been undone when 

removing the heatsink from the electrical housing. 

2.3.4 

Connect the line voltage supply wires to the 

luminaire input wires using the pre-installed lever nuts. 
 

2.4 Wiring the Luminaire – Emergency Battery Pack 
(EM) Luminaires only 
2.4.1 

Follow steps 2.3.1 to 2.3.3 

2.4.2 

Connect the line voltage supply wires to the 

luminaire input wires using the pre-installed lever nuts. 
For the emergency battery pack, both the switched 
(white/red wire from battery) and unswitched 
(orange/black wire from battery) lines are run through 
surge protection devices. The unswitched line will be 
labeled on the surge protection device. 

2.4.3 

Connect the battery pack inverter (red and white 

wires with clear, plastic caps) to enable the battery back-
up 

CAUTION:

 

The emergency battery pack must be 

allowed to charge for 24 hours prior to testing operation. 
The battery will continuously discharge until it is drained 
and will begin charging when the luminaire is energized. 

CAUTION: 

Luminaires with an emergency battery pack 

cannot be mounted higher than 10.74 ft. from the ground 

in order to comply with UL emergency lighting 1-ft candle 
criteria 

 
2.5 Wiring the Luminaire – Two Independent Circuit 
(2CI) Luminaires only 
2.5.1 

Follow steps 2.3.1 to 2.3.3 

2.5.2 

Connect the line voltage supply wires to the 

luminaire input wires using the pre-installed lever nuts. 
For the 2CI option, there should be 2 identical drivers 
present in the luminaire. The driver that is intended to be 
powered by the building’s inverter has an “unswitched” 
label from the factory. The wire color for the unswitched 
line will be variable depending on the performance 
package chosen. 

 

 

2.6 Attaching Heatsink to Electrical Housing (Figure 
4) 
2.6.1 

Bring the heatsink close to the electrical housing 

and insert the 4 guiding pins on the heatsink into the 4 
guiding holes in of the electrical housing 

2.6.2 

Making sure not to pinch any wires or chains, slide 

the heatsink until it makes contact with the electrical 
housing. 

2.6.3 

Tighten the 6 screws to 20-25 in-lbs. to ensure a 

watertight seal and a secure connection of the heatsink 
to the electrical housing.   

 

WARNING 

FAILURE TO TIGHTEN HOUSING SCREWS COULD 
CAUSE LUMINAIRE TO FALL RESULTING IN 
INJURY, DEATH OR SERIOUS PROPERTY DAMAGE. 
 

AVERTISSEMENT  

NE PAS SERRER CORRECTEMENT LA VIS DE 
RÉGLAGE PEUT PROVOQUER LA CHUTE DE LA 
FIXATION ET CAUSER DES BLESSURES, 
PROVOQUER LA MORT OU DE SÉRIEUX 
DOMMAGES MATÉRIELS. 

 

Figure 4 

 

GR2676 

 

3” mount 

5” mount 
4” mount 