Operation Manual - LR7 Wall Control
Document: 0525-075
Ver. 2 190912
Operation Manual
LR7 Wall Controller
24
13.03.02. Setting Temperature Set back
NOTE
The Set back mode Cool to and Heat to limits can only be adjusted from the temperature set back menu.
In the occurrence of when the unit’s setpoint (prior to Set back operation) is below the Heat to limit or higher
than the Cool to limit, the unit’s setpoint will automatically become the new Set back limit.
1. Press the
PROG
button to enter program Menu
2. Press the
or
buttons to navigate to Program Menu 03.
3. Press the
PROG
button to enter Program Menu 03. Display will show set back display
ON
field is blinking.
4. Press the
PROG
button to enter On Program Menu.