Installation and Commissioning Guide
Split Ducted Units
PRELIMINARY DATA ONLY
Ver. 3.03 220620
THIS LABEL TO BE REMOVED ON SIGN-OFF
7
Installation and Commissioning Guide - Split Ducted Indoor Unit
Doc. No.0525-084
Ver. 3 22xxxx
EVV180S
OVERALL NOMINAL DIMENSION (H X W X D)
= 435 X 1420 X 680
SUPPLY DUCT (H X W) = 300 X 715
RETURN DUCT = 360 X 1140
CONDENSATE DRAIN CONNECTION = 20mm OD
UNIT MODEL NUMBER
UNIT WEIGHT
(kg)
EVV180S
69
SUPPLY
AIR
715
311
311
1420 O/A
1140
79
118
630
20
20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
590
40
50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
11
1315
(MTG C-C DIST)
11
TOP VIEW
FRONT VIEW
SIDE VIEW
SUPPLY
AIR
715
311
311
1420 O/A
1140
79
118
630
20
20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
590
40
50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
11
1315
(MTG C-C DIST)
11
SUPPLY
AIR
715
311
311
1420 O/A
1140
79
118
630
20
20
435
O/A
INDOOR COIL
1375
90
130
SUPPLY AIR
590
40
50
680 O/A
360
50
25
110
300
25
RETURN
AIR
EC
INDOOR
FAN
EC
INDOOR
FAN
11
1315
(MTG C-C DIST)
11
DUCT WORK
DUCT WORK
LEFT
SERVICE
CLEARANCE
800 mm
*RIGHT
SERVICE
CLEARANCE
800 mm
EC
ID FAN
EC
ID FAN
INDOOR COIL
HEIGHT CLEARANCE = 410mm
MINIMUM SERVICE ACCESS AREAS AND AIRFLOW CLEARANCES
TOP VIEW
*
Electrical box and/or
pipe connections are
located on the Right
side of the indoor unit.
NOTES:
1. Do not scale drawing.
All dimensions are in mm unless
specified.
2. Service Clearances given are suggested
minimum based on the condition that
the spaces around the units are free
from any obstructions and a walkway
passage of 1000mm between the units
or between the unit and the outside
perimeter is available.
3. Minimum service access clearances are
responsibilities of the installer, ActronAir
will not be held liable for any extra
charges incurred due to lack of access.
• Left Service Clearance can be 100mm
minimum if Right Service Clearance is
applicable.
• Right Service Clearance can be
600mm minimum if Left Service
Clearance is applicable.
• Height Service Clearance can be
100mm minimum if Right Service
Clearance is applicable.
THIRD ANGLE
PROJECTION