background image

12

0x0006

DO7 state

R/W

0

opening 1

closing

0x0007

DO8 state

R/W

0

opening 1

closing

0x0009

DO9 state

R/W

0

opening 1

closing

0x000A

DO10 state

R/W

0

opening 1

closing

0x000B

DO11 state

R/W

0

opening 1

closing

0x000C

DO12 state

R/W

0

opening 1

closing

0x000D

DO13 state

R/W

0

opening 1

closing

0x000E

DO14 state

R/W

0

opening 1

closing

0x000F

DO15 state

R/W

0

opening 1

closing

0x0010-0x002C

DO16—DO44 state

R/W

0

opening 1

closing

5.5 Communication examples
Example 1: Read the current switch status of the remote communication unit with instrument address 2.

Send: 0x02,0x03,0x50,0x10,0x00,0x02,0XD4,0xFD
Return: 0x02,0x03,0x04,0x00,0x00,0x00,0x03,0x89,0x32

Note: The first and second channel switches of the remote communication unit with instrument address 2 are

connected, and the remaining 30 channel switches are disconnected.
Example 2: Read the status of 1 to 5 switches

Send: 0x01,0x02,0x00,0x00,0x00,0x05,0xB8,0x09

Return: 0x01,0x02,0x01,0x10,0xA0,0x44
Note: 0x 10 is converted to a binary number of 0001,000, that is, the fifth switch is in the connected status, and

the rest are in the disconnected status.
Example 3: Read the status of 1 to 32 switches.

Send: 0x01,0x02,0x00,0x00,0x00,0x20,0x79,0xD2

Return: 0x01,0x02,0x04,0x00,0x00,0x8E,0x04,0x9F,0x81
Note: 0x00,0x00,0x8E,0x04 are converted to binary numbers of 0000,0000,0000,0000,1000,1110,0000,0100,

that is, the switches of paths 18, 19, 20, 24 and 27 are in the connected status, and the rest are in the disconnected
status.
Example 4: Read the status of 17 to 32 switches.

Send: 0x01,0x02,0x00,0x10,0x00,0x10,0x78,0x03

Return: 0x01,0x02,0x02,0x8E,0x04,0xDD,0xDB
Note: 0x8E,0x04 are converted to binary numbers of 1000,1110,0000,0100, that is, the switches of paths 18, 19,

20, 24 and 27 are in the connected status, and the rest are in the disconnected status.
Example 5: Set the current time.

Send: 0x01,0x10,0x10,0x2C,0x00,0x03,0x06,0x15,0x02,0x18,0x11,0x06,0x1E, 0xDD,0x1D
Return: 0x01,0x10,0x10,0x2C,0x00,0x03,0x45,0x01
Note: It indicates that the time is set to 17:06:30 on February 24, 2021 (note the BCD code format).

Summary of Contents for ARTU Series

Page 1: ...426 ARTU Series of Remote Terminal Units Installation and Operation Manual V1 0 Acrel Co Ltd...

Page 2: ...reproduced or disseminated in any form otherwise all consequences shall be borne by the offender The Company reserves all legal rights The Company reserves the right to modify the product specificati...

Page 3: ...ettings 13 6 1 1 Dial code definition 13 6 1 2 Address settings 13 6 1 3 Baud rate settings 13 6 1 4 Mode settings 13 6 1 5 Format settings 13 6 2 Modbus function code description 14 6 2 1 Exception r...

Page 4: ...ion network specification Part 1 Modbus application protocol GB T 19582 2 2008 Modbus industrial automation network specification Part 2 Modbus protocol implementation guide over serial link GB T13729...

Page 5: ...ator lights Optional features Model CE 1 path ethernet TCP IP protocol 10M 100M self adaptive MKA18 Switch input 18 path DI active AC 220V MJ12 Switch output 12 path DO output mode Relay normally open...

Page 6: ...0 70 Relative humidity 95 without condensation Altitude 2500m 4 Installation and Wiring 4 1 Outline dimensions 4 2 Installation methods Guide rail and wall hanging double installation methods are used...

Page 7: ...32 33 34 35 36 38 39 37 40 40 DI9 48 39 38 47 46 45 44 43 42 41 7 17 5 2 1 N L 32DI2DO 64 61 63 62 60 59 58 57 56 55 54 53 52 51 50 49 16DI8AI2DO A1 B1 A2 B2 DI2 DI3 DI DI1 21 22 24 25 26 30 31 32 33...

Page 8: ...r lights Modules Specifications MKA18 MJ12 MA84 Indicator light description 1 POW refers to the power light 2 The number refers to the channel number the odd number refers to the red light and the eve...

Page 9: ...6 32 Active input node 12V 5 Communication Description 5 1 Full parameter information of instrument Modbus function code 03 03H 04 04H can be used to access all contents in the address table and funct...

Page 10: ...int16 R W 4 0x1452 high 255 low 255 0x1453 high 255 low 0 0x1454 0x1455 Gateway Address Uint16 R W 4 0x1454 high 192 low168 0x1455 high 0 low0 0x1456 Port Number Uint16 R W 2 Default 5000 0x2000 Main...

Page 11: ...7 Statue Uint16 R 2 0 opening 1 closing 0x5012 DI48 33 Statue Uint16 R 2 0 opening 1 closing 0x5013 DI64 49 Statue Uint16 R 2 0 opening 1 closing 0x5014 DI80 65 Statue Uint16 R 2 0 opening 1 closing 0...

Page 12: ...2 1 0 20mA 2 4 20mA 3 0 5V 4 1 5V 0x5501 AI 1High Int16 R W 2 0x5502 AI1 Low Int16 R W 2 0x5503 AI2 Style Uint16 R W 2 1 0 20mA 2 4 20mA 3 0 5V 4 1 5V 0x5504 AI2 High Int16 R W 2 0x5505 AI2 Low Int16...

Page 13: ...event record number Uint16 R 2 0xD001 Action date High byte year Low byte month Uint16 R 2 0xD002 Action time High byte day Low byte time Uint16 R 2 0xD003 Action minutes and seconds High byte minute...

Page 14: ...4 DI5 state BIT R 0 opening 1 closing 0x0005 DI6 state BIT R 0 opening 1 closing 0x0006 DI7 state BIT R 0 opening 1 closing 0x0007 DI8 state BIT R 0 opening 1 closing 0x0009 DI9 state BIT R 0 opening...

Page 15: ...0x01 0x02 0x01 0x10 0xA0 0x44 Note 0x 10 is converted to a binary number of 0001 000 that is the fifth switch is in the connected status and the rest are in the disconnected status Example 3 Read the...

Page 16: ...ings 6 1 1 Dial code definition 1 2 3 4 5 6 7 8 9 10 Address settings 1 0 0 0 0 Baud rate settings 0 0 Mode settings 0 Communication mode settings 0 0 6 1 2 Address settings Dial code 1 Dial code 2 Di...

Page 17: ...ritten 6 2 2 Status of the used Modbus 01H 02H function Reading required by the upper computer MODBUS 01H 02H function Address Function Address Data CRC check BYTE BYTE WORD WORD WORD XX XX 01H 02H XX...

Page 18: ...on Exception error code data CRC check BYTE BYTE BYTE WORD XX XX 85H XX 02H address error 03H data error XXXX CRC check value 6 2 5 Write multiple data by using Modbus 10H function Write multiple data...

Page 19: ...ing to the station number and baud rate of the module in the protocol format At this time the communication indicator light of the module flashes indicating that the module has received the command of...

Page 20: ...ax 0086 21 69158303 Web site www acrel electric com E mail ACREL008 vip 163 com Postcode 201801 Manufacturer Jiangsu Acrel Electrical Manufacturing Co LTD Address No 5 Dongmeng Road Dongmeng industria...

Reviews: