62
Installation
Pipe installation - U trap required
The condensate disposal piping must have a trap and the piping must be pitched away from the unit not less than 1/4"
inch per foot (20mm per meter).A piece of single hose from the trap to the drain line is used for simple removal.
Flexible hose - recommended
1. Since hose may change in length from +2% to –4%
2. Absorb unit vibration
J
L
Optional Cleanout
(21mm Per Meter)
1/4" Per Foot
H
Strainer
Two-way valve
Flexible Pipe
Return water pipe
Water supply pipe
Water pressure gauge
Valve
Switch
Thermometer