57
ADDITIONAL CHARGE
•
The refrigerant gas has already charged into the outdoor unit. For the piping length of 5m. Additional refrigerant
charge after vacuuming is not necessary.
•
When the piping length is more than 5m, please use the table below (unit in gram).
COOLING
MODEL
ACC 10C
ACC 15C
ACC 20C
ACC 25C
ACC 30C
ACC 40C
ACC 50C
ACC 60C
7m
30
30
30
76
100
100
100
100
10m
75
75
75
190
250
250
250
250
15m
-
-
150
380
500
500
500
500
20m
-
-
-
-
750
750
750
750
35m
-
-
-
-
1500
1500
1500
1500
HEAT PUMP
MODEL
ACC 10CR
ACC 15CR
ACC 20CR
ACC 25CR
ACC 30CR
ACC 40CR
ACC 50CR
ACC 60CR
7m
40
40
50
100
100
100
100
100
10m
100
100
125
250
250
250
250
250
15m
-
-
250
500
500
500
500
500
20m
-
-
-
-
750
750
750
750
35m
-
-
-
-
1500
1500
1500
1500
OVERALL CHECKING
•
Ensure the following, in particular :
1) The unit is mounted solidly and rigid in position.
2) Piping and connections are leak proof after charging.
3) Proper wiring has been done.
•
Drainage check - pour some water into drain pan.
•
Test run
1) Conduct a test run after water drainage test and gas leakage test.
2) Watch out for the following :
a) Is the electric plug firmly inserted into the socket?
b) Is there any abnormal sound from unit?
c) Is there any abnormal vibrations with regard to unit itself or piping?
d) Is there smooth drainage of water?
•
Check that :
1) Outdoor fan is running, with warm air blowing off the outdoor unit (cooling cycle).
2) Indoor blower is running and discharge cool air (cooling cycle).
3) Suction (low side) pressure as recommended is before this.
4) The remote controller incorporate a 3 minute delay in there circuit. Thus, it requires about 3
minutes before the outdoor unit can start up.
CAUTION FOR R407C
Do not top-up when servicing leak, as this will reduce the unit performance. Vacuum the unit
thoroughly and then charge the unit with fresh R407C according to the amount recommended
in the specification.
CAUTION FOR R407C
Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist air.
The POE oil in the compressor and piping can absorb moisture from air.
Summary of Contents for ACC 10 C/CR
Page 16: ...15 MODEL ACC50C MODEL ACC60C...
Page 26: ...25 MODEL ACC 60 ALC 60C FOR EXPORT SPEC WITH MC MODEL ACC 60C ALC 60C FOR LOCAL SPEC...
Page 27: ...26 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Page 28: ...27 MODEL ACC 10CR 15CR ALC A4LC 10BR 15BR...
Page 29: ...28 MODEL ACC 20CR 25CR ALC A4LC 20BR 25BR...
Page 30: ...29 MODEL ACC 30CR ALC A4LC 30CR...
Page 31: ...30 MODEL ACC 40CR 50CR ALC A4LC 40CR 50CR...
Page 32: ...31 MODEL ACC 60CR ALC 60CR...
Page 33: ...32 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Page 37: ...36 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 38: ...37 MODEL ACC 10 15CR ALC A4LC 10 15BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 39: ...38 MODEL ACC 20 25CR ALC A4LC 20 25BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 40: ...39 MODEL ACC 30CR ALC A4LC 30CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 41: ...40 MODEL ACC 40 50CR ALC A4LC 40 50CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 42: ...41 MODEL ACC 60CR ALC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 43: ...42 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...