13
MODEL : ACC20C/ALC20B
Indoor DB Indoor WB
Capacity
Outdoor DB, ° C
° C
° C
kW
19.4
25
30
35
40
46
26.7
13.9
TC
5.264
5.010
4.783
4.556
4.330
4.058
SC
4.788
4.634
4.497
4.360
4.223
4.058
15
TC
5.607
5.313
5.051
4.788
4.526
4.211
SC
4.749
4.585
4.439
4.292
4.146
3.970
18
TC
6.542
6.139
5.780
5.420
5.061
4.629
SC
4.643
4.451
4.279
4.108
3.936
3.730
19.4
TC
6.979
6.525
6.120
5.715
5.310
4.824
SC
4.594
4.388
4.205
4.022
3.838
3.618
20
TC
7.166
6.694
6.272
5.851
5.429
4.923
SC
4.572
4.347
4.145
3.944
3.742
3.501
22
TC
7.789
7.255
6.779
6.302
5.825
5.253
SC
4.502
4.209
3.947
3.685
3.424
3.110
24
TC
8.413
7.817
7.286
6.754
6.222
5.584
SC
4.431
4.070
3.749
3.427
3.105
2.719
MODEL : ACC25C/ALC25B
Indoor DB Indoor WB
Capacity
Outdoor DB, ° C
° C
° C
kW
19.4
25
30
35
40
46
26.7
13.9
TC
6.800
6.463
6.163
5.863
5.563
5.202
SC
5.808
5.680
5.567
5.453
5.339
5.202
15
TC
7.260
6.864
6.510
6.156
5.802
5.377
SC
5.689
5.557
5.439
5.321
5.203
5.061
18
TC
8.516
7.955
7.455
6.954
6.454
5.853
SC
5.366
5.221
5.091
4.961
4.831
4.676
19.4
TC
9.102
8.465
7.896
7.327
6.758
6.076
SC
5.215
5.064
4.929
4.793
4.658
4.496
20
TC
9.353
8.693
8.103
7.514
6.924
6.217
SC
5.151
4.978
4.825
4.671
4.517
4.332
22
TC
10.190
9.453
8.795
8.136
7.478
6.688
SC
4.935
4.693
4.477
4.261
4.045
3.786
24
TC
11.027
10.213
9.486
8.758
8.031
7.159
SC
4.720
4.408
4.130
3.852
3.574
3.240
All the data above are based on 26.7°C entering DB. To obtain data for different entering DB, please use the
formula below :
Sensible capacity (EDB) = Sensible capacity (26.7) + 1.23 x L/s x (1 - BPF) ( EDB - 26.7 ) / 1000
Where, BPF = Bypass factor
EDB = Entering dry bulb temperature, ° C
Model
ACC10C
ACC15C
ACC20C
ACC25C
Bypass factor
0.61
0.56
0.60
0.61
Summary of Contents for ACC 10 C/CR
Page 16: ...15 MODEL ACC50C MODEL ACC60C...
Page 26: ...25 MODEL ACC 60 ALC 60C FOR EXPORT SPEC WITH MC MODEL ACC 60C ALC 60C FOR LOCAL SPEC...
Page 27: ...26 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Page 28: ...27 MODEL ACC 10CR 15CR ALC A4LC 10BR 15BR...
Page 29: ...28 MODEL ACC 20CR 25CR ALC A4LC 20BR 25BR...
Page 30: ...29 MODEL ACC 30CR ALC A4LC 30CR...
Page 31: ...30 MODEL ACC 40CR 50CR ALC A4LC 40CR 50CR...
Page 32: ...31 MODEL ACC 60CR ALC 60CR...
Page 33: ...32 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL C3 0BCC...
Page 37: ...36 MODEL ACC 60C AMC 60C FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 38: ...37 MODEL ACC 10 15CR ALC A4LC 10 15BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 39: ...38 MODEL ACC 20 25CR ALC A4LC 20 25BR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 40: ...39 MODEL ACC 30CR ALC A4LC 30CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 41: ...40 MODEL ACC 40 50CR ALC A4LC 40 50CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 42: ...41 MODEL ACC 60CR ALC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...
Page 43: ...42 MODEL ACC 60CR AMC 60CR FOR EXPORT SPEC WITH SLM CONTROL U1 4...