45
c) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is
about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
f)
Normally, the R407C cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if
the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
g) When servicing leak, the top up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made up of three different components, may have changed during the leak. Consequently, a top
up may not ensure that the R407C in the system is of original composition. This composition shift may
adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
Dip-pipe
I
nvert cylinder
without dip-pipe
Liquid
withdrawal
R32 / R125 / R134
23% / 25% / 52%
33% / 33% / 34%
Composition of R407C in vapour phase
is different from liquid phase.
Summary of Contents for A4AC100C
Page 19: ...17 5 2 Menu Structures Menu Structure Diagram for Chiller...
Page 140: ...138 9 WIRING DIAGRAMS MODEL A4AC AMAC20C...
Page 141: ...139 MODEL A4AC AMAC25 30C...
Page 143: ...141 MODEL A4AC AMAC80 100C WITH ISOLATED SWITCH...
Page 144: ...142 MODEL A4AC AMAC 120 150C WITH ISOLATED SWITCH...
Page 145: ...143 MODEL A4AC AMAC80 100C WITH TERMINAL BLOCK...
Page 146: ...144 MODEL A4AC AMAC 120 150C WITH TERMINAL BLOCK...
Page 147: ...145 MODEL AMAC 25 30CR...
Page 149: ...147 MODEL A4AC AMAC 80 100CR WITH ISOLATED SWITCH...
Page 150: ...148 MODEL A4AC AMAC 120 150CR WITH ISOLATED SWITCH...
Page 151: ...149 MODEL A4AC AMAC 80 100CR WITH TERMINAL BLOCK...
Page 152: ...150 MODEL A4AC AMAC 120 150CR WITH TERMINAL BLOCK...
Page 153: ...151 MODEL A5AC20 25CR...