11. TROUBLESHOOTING
When any malfunction is occurred, immediately switch off the power supply to the unit, and contact the
local dealer, if necessary. Some simple troubleshooting tips are given below:
Phase Proctector (Optional)
The unit with Scroll Compressor can only rotate in one direction. For this reason, a protective device
(phase proctector) is fitted to prevent incorrect wiring of the electrical phases. When the three phases
are not connected correctly, the phase protector operates, and the unit will not start. This devise is located
in the control box of model AMAC/ A4AC80~150C/CR.
The following tables shows the LED indicator light for phase proctector under normal operation and fault
coonditions.
Notes: 1. “+” indicates additional for PP01 phase proctector.
2. When R phase missing. no LED or buzzer will indicate the error, but relay 71 and 81 will cut off.
LED
PW
P_R
P_S
P_T
Description
(Red)
(Yellow)
(Yellow)
(Yellow)
Normal operation
○
●
●
●
-
Reverse phase
◑
◑
◑
◑
Swith off the unit. Check the 3 phase wiring.
T phase missing
◑
●
●
◑
Swith off the unit. Check the 3 phase wiring.
S phase missing
◑
●
◑
●
Swith off the unit. Check the 3 phase wiring.
R phase missing
●
●
●
●
Swith off the unit. Check the 3 phase wiring.
S & T phase missing
+
◑
●
◑
◑
Swith off the unit. Check the 3 phase wiring.
Overload
+
◑
●
●
●
High discharge temperature. Check the refrigerant system.
Sensor missing
+
◑
○
○
○
Swtich off the unit. Plug in sensor.
Actions
○
On
●
Off
◑
Fast Blink
SYMPTONS PROBLEM
CAUSES
REMEDIAL
ACTION
1. Compressor
does
not start.
•
No
power
supply.
•
Fuses blown or automatic circuit
break down open.
•
Defective contactor or coil.
•
Unit is stopped because safety
device has tripped.
•
Loose
wires.
•
Compressor
faulty.
•
Check power supply.
•
Look for short circuit or grounded
wires in motor windings. Replace
fuses and reset circuit breakers
when the fault has been corrected.
Check tightness and soundness of
all electrical connections.
•
Repair
or
replace.
•
Determine the type of safety shut
down and correct the default before
the unit is restarted.
•
Check wire connections and
tighten terminal screws.
•
Contact
local
dealer.
2. Fan does not work.
•
No
power
supply.
•
Fan
motor
faulty.
•
Check power supply.
•
Contact
local
dealer
3. Unit does work, but
insufficient cooling.
•
Thermostats setting too high.
•
Condenser
coil
dirty.
•
Obstacle blocking air inlet or
outlet of the unit.
•
Insufficient refrigerant in the
system.
•
Improper water flow rate,
•
Water in the system is
contaminated.
•
Reset
thermostat.
•
Contact
local
dealer.
•
Remove
obstacles.
•
Contact
local
dealer.
•
Contact
local
dealer.
•
Contact
local
dealer.
4. Flow switch error.
•
No water in the system.
•
Low water level in the system.
•
Phase missing or phase reversed
•
Check water supply.
•
Check water supply.
•
Check phase protector
Summary of Contents for A4AC100C
Page 19: ...17 5 2 Menu Structures Menu Structure Diagram for Chiller...
Page 140: ...138 9 WIRING DIAGRAMS MODEL A4AC AMAC20C...
Page 141: ...139 MODEL A4AC AMAC25 30C...
Page 143: ...141 MODEL A4AC AMAC80 100C WITH ISOLATED SWITCH...
Page 144: ...142 MODEL A4AC AMAC 120 150C WITH ISOLATED SWITCH...
Page 145: ...143 MODEL A4AC AMAC80 100C WITH TERMINAL BLOCK...
Page 146: ...144 MODEL A4AC AMAC 120 150C WITH TERMINAL BLOCK...
Page 147: ...145 MODEL AMAC 25 30CR...
Page 149: ...147 MODEL A4AC AMAC 80 100CR WITH ISOLATED SWITCH...
Page 150: ...148 MODEL A4AC AMAC 120 150CR WITH ISOLATED SWITCH...
Page 151: ...149 MODEL A4AC AMAC 80 100CR WITH TERMINAL BLOCK...
Page 152: ...150 MODEL A4AC AMAC 120 150CR WITH TERMINAL BLOCK...
Page 153: ...151 MODEL A5AC20 25CR...