43
COOL MODE ANTIFREEZE
Unit
Default
Min
Max
Resolution
A1
Antifreeze heater set-point
°C (F)
5 (41)
-40 (-40)
40 (104)
1
A2
Antifreeze heater differential
°C (F)
2 (3.6)
0.4 (0.7)
10 (18)
0.1
A3
Antifreeze sensor select
Flag
0
0
1
1
0=Leaving water, 1=Entering water
(leaving)
A4
Antifreeze alarm set-point
°C (F)
3 (37)
-40 (-40)
40(104)
1
A5
Antifreeze alarm differential
°C (F)
2 (3.6)
0.4 (0.7)
10 (18)
0.1
ALARM AND CONTACT
Unit
Default
Min
Max
Resolution
P1
Flow switch confirmation time
sec
5
0
199
1
P2
Flow switch alarm delay at pump start
sec
120
0
199
1
P3
Low pressure alarm delay at compressor start up
sec
30
0
199
1
P4
Comp overload alarm reset type
Flag
0
0
1
1
0=Manual reset, 1=Auto reset
(manual)
P5
High pressure alarm reset type
Flag
1
0
1
1
0=Manual reset, 1=Auto reset
(auto)
P6
Low pressure alarm reset
Flag
1
0
1
1
0=Manual reset, 1=Auto reset
(auto)
P7
Fan overload alarm reset type
Flag
1
0
1
1
0=Manual reset, 1=Auto reset
(auto)
P8
Pump overload alarm reset type
Flag
0
0
1
1
0=Manual reset, 1=Auto reset
(manual)
P9
Flow switch alarm reset type
Flag
0
0
1
1
0=Manual reset, 1=Auto reset
(manual)
P10
Auxiliary alarm reset type
Flag
1
0
1
1
0=Manual reset, 1=Auto reset
(auto)
P11
Antifreeze alarm reset type
Flag
0
0
1
1
0=Manual reset, 1=Auto reset
(manual)
P12
Comp overload contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P13
High pressure contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P14
Low pressure contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P15
Fan overload contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P16
Pump overload contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P17
Flow switch contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P18
External alarm contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
P19
Defrost end contact type
Flag
0
0
1
1
0=Normally close(NC) 1=Normally open(NO)
(NC)
INVERTER
Unit
Default
Min
Max
Resolution
V1
Compressor frequency
Hz
Auto
0
120
1
V2
EXV Opening
Flag
Auto
0
480
1
V3
Compressor manual setting
0= disable 1= enable
V4
EXV Manual setting
0=disable 1= enable
V5
Defrost Mode
0= disable 1= enable
1
Flag
0(disable)
0
1
0
1
1
Flag
0(disable)
0
1
1
Flag
0(disable)
Summary of Contents for A4AC100C
Page 19: ...17 5 2 Menu Structures Menu Structure Diagram for Chiller...
Page 140: ...138 9 WIRING DIAGRAMS MODEL A4AC AMAC20C...
Page 141: ...139 MODEL A4AC AMAC25 30C...
Page 143: ...141 MODEL A4AC AMAC80 100C WITH ISOLATED SWITCH...
Page 144: ...142 MODEL A4AC AMAC 120 150C WITH ISOLATED SWITCH...
Page 145: ...143 MODEL A4AC AMAC80 100C WITH TERMINAL BLOCK...
Page 146: ...144 MODEL A4AC AMAC 120 150C WITH TERMINAL BLOCK...
Page 147: ...145 MODEL AMAC 25 30CR...
Page 149: ...147 MODEL A4AC AMAC 80 100CR WITH ISOLATED SWITCH...
Page 150: ...148 MODEL A4AC AMAC 120 150CR WITH ISOLATED SWITCH...
Page 151: ...149 MODEL A4AC AMAC 80 100CR WITH TERMINAL BLOCK...
Page 152: ...150 MODEL A4AC AMAC 120 150CR WITH TERMINAL BLOCK...
Page 153: ...151 MODEL A5AC20 25CR...