ACS Marvair CommStat 4 Installation And Operation Manual Download Page 9

CommStat

 4 

 

 

Modbus Adapter 

 

 

Installation & Operation 

 

 

 

 

Page  9 

CommStat™ 4

 

Modbus Read Registers 

The adapter supports Modbus TCP/IP read requests from the Master system through port 502 of the configured IP address of the interface adapter.   
The read registers are detailed in the table below. 

Register 

Source 

Value

 

Description 

Comments

 

40001 

Master  Master's firmware revision number 

[Self-explanatory] 

Must be less than 255 

40002 

Master  Protocol Version Number (3 or 4) 

[Self-explanatory] 

[Self-explanatory] 

40003 

Master  Setting #2 

F/C 

0: Celsius, 1: Fahrenheit 

40004 

Master  Setting #3 

Changeover days 

Half Days, range 1 to 14 

40005 

Master  Setting #4 

Cool set point 

See CommStat

TM

 4 manual

 

40006 

Master  Setting #5 

Heat set point 

See CommStat

TM

 4 manual 

40007 

Master  Setting #6 

High building temp 1 set point 

See CommStat

TM

 4 manual 

40008 

Master  Setting #7 

High building temp 2 set point 

See CommStat

TM

 4 manual

 

40009 

Master  Setting #8 

Low building temp set point 

See CommStat

TM

 4 manual 

40010 

Master  Setting #9 

Blower on 

0: Off, 1: On 

40011 

Master  Setting #10 

High voltage input enable / alarm output enable 

 

40012 

Master  Setting #11 

Anti-short cycle timer 

Number of minutes (see CommStat

TM

 4 manual) 

40013 

Master  Setting #12 

Stage 1 Differential 

See CommStat

TM

 4 manual

 

40014 

Master  Setting #13 

Stage 2 differential 

See CommStat

TM

 4 manual 

40015 

Master  Setting #14 

Off differential 

See CommStat

TM

 4 manual 

40016 

Master  Setting #15 

Blower off time delay 

See CommStat

TM

 4 manual

 

40017 

Master  Setting #16 

Operational units when generator is used 

[Self-explanatory]

 

40018 

Master  Setting #17 

Smoke auto reset 

0: Manual Reset, 3 to 10: # minutes until auto reset

 

40019 

Master  Setting #18 

Smoke relay 

0: Normally Open, 1: Normally Closed

 

40020 

Master  Setting #19 

ECON mode enable 

0: No, 1: Yes, 2: Verizon special setting 

40021 

Master  Setting #20 

Multiple sensors 

0: No, 1: Yes 

40022 

Master  Setting #21 

Aux. 1 relay 

0: Normally Open, 1: Normally Closed, 2: Off 

40023 

Master  Setting #22 

Aux. 2 relay 

0: Normally Open, 1: Normally Closed, 2: Off

 

40024 

Master  Setting #23 

Excessive cycle 

0: Off, Non-Zero: # cycles allowed in 2 hour period 

40025 

Master  Setting #24 

Language 

0: English, 1: Spanish, 2: French 

40026 

Master  Setting #25 

AC / HP system 

0: HP, 1: One AC, 2: Two AC

 

40027 

Master  Setting #26 

Master/slave 

0: Slave, 1: Master

 

40028 

Master  Setting #27 

Stage 3 differential 

See CommStat

TM

 4 manual

 

40029 

Master  Setting #28 

Stage 4 differential 

See CommStat

TM

 4 manual 

40030 

Master  Setting #29 

Stage 5 differential 

See CommStat

TM

 4 manual

 

40031 

Master  Setting #30 

Stage 6 differential 

See CommStat

TM

 4 manual 

 

Table 1: 

CommStat™4 

Modbus Read Registers 

Summary of Contents for Marvair CommStat 4

Page 1: ...AirX Climate Solutions Brand P O Box 400 Cordele Georgia 31010 156 Seedling Drive Cordele Georgia 31015 229 273 3636 Fax 229 273 5154 E mail marvairsales airxcs com Internet www marvair com The most...

Page 2: ...and EXPERIENCED PEOPLE 4 USE COMMON SENSE and BE SAFETY CONSCIOUS This is the safety alert symbol When you see this symbol in the manual be alert to the potential for personnel injury or equipment da...

Page 3: ...not exceed 15ft 457cm including all necessary conduit routing Note that the adapter must be installed inside the shelter it is not suitable for installation either inside an HVAC unit or where exposur...

Page 4: ...CommStat 4 Modbus Adapter Installation Operation Page 4 Figure 1 Modbus Interface Adapter External Connections Figure 2 Modbus Interface Adapter Power LED...

Page 5: ...1 19 If a different IP address is required a laptop can be used to re configure the adapter In order to establish communications the laptop must have and IP address within the same subnet as the adapt...

Page 6: ...Installation Operation Page 6 Click Change adapter settings Figure 5 Network and Sharing Center Right click on the Local Area Connection and select Properties from the drop down menu Figure 6 Local A...

Page 7: ...pdated Click Use the following IP address and enter 192 168 1 100 in the IP address field and 255 255 255 0 in the Subnet mask field Do not enter any values into any of the other IP address fields The...

Page 8: ...anges The adapter will reboot and after 60 seconds the new network configuration will be active Note that if the new network parameters are on a different subnet the browser will lose communications t...

Page 9: ...aster Setting 12 Stage 1 Differential See CommStatTM 4 manual 40014 Master Setting 13 Stage 2 differential See CommStatTM 4 manual 40015 Master Setting 14 Off differential See CommStatTM 4 manual 4001...

Page 10: ...slave unit 1 Self explanatory See note 3 40050 Master Output command master to slave unit 2 Self explanatory See note 3 40051 Master Saved value of master unit 1 outputs Self explanatory Internal Use...

Page 11: ...3 Bit 7 is always clear if bit 6 is set this unit is outputting to Y if bit 5 is set this unit is outputting to 2 if bit 4 is set this unit is outputting to O if bit 3 is set this unit is outputting t...

Page 12: ...e is 12 it is in stage 0 if value is 13 it is in stage 1 heating if value is 14 it is in stage 2 heating if value is 15 it is in stage 3 heating if value is 16 it is in stage 4 heating 6 If bit 7 is s...

Page 13: ...igh voltage input enable alarm output enable 40111 Remote Setting 11 Anti short cycle timer 40112 Remote Setting 12 Stage 1 Differential 40113 Remote Setting 13 Stage 2 differential 40114 Remote Setti...

Page 14: ...rd 40143 Remote Function code The purpose of this communication signal Table 2 CommStat 4 Modbus Write Registers The process to update parameters in the CommStat 4 unit is controlled through the use o...

Page 15: ...ABS Thermoplastic flammability rating UL94 5VA External Connections Power Supply Terminal Block The two position power input terminal block has the following connections Wire Color Label Description B...

Page 16: ...el 1 NC 2 Ground 3 RS 485 RX TX A 4 RS 485 RX TX B 5 VCC 6 NC Figure 13 RJ11 Connector Pinout Ethernet RJ45 Connector The female RJ45 socket provides the Ethernet connection for the Master system The...

Page 17: ...CommStat 4 Modbus Adapter Installation Operation Page 17 Dimensional Drawings Figure 15 Adapter Enclosure Dimensions 1...

Page 18: ...CommStat 4 Modbus Adapter Installation Operation Page 18 Figure 16 Adapter Enclosure Dimensions 2...

Reviews: