CommStat
™
4
Modbus Adapter
Installation & Operation
Page 14
Register
Source
Value
Description
40131
Remote
Setting #31
Stage 7 differential
40132
Remote
Setting #32
Stage 8 differential
40133
Remote
Setting #33
Stage 9 differential
40134
Remote
Setting #34
Stage 10 differential
40135
Remote
Setting #35
Stage 11 differential
40136
Remote
Setting #36
Stage 12 differential
40137
Remote
Setting #37
Total Number of Units
40138
Remote
Setting #38
Stage 2 differential in econ cooling mode
40139
Remote
Controller On/Off
Whether the controller should be on or off
40140
Remote
Lead unit
Which unit should be the lead unit
40141
Remote
Password #1
First byte of the password
40142
Remote
Password #2
Second bytes of the password
40143
Remote
Function code
The purpose of this communication signal
Table 2:
CommStat
™
4
Modbus Write Registers
The process to update parameters in the
CommStat 4
unit is controlled through the use of register 40101. The sequence of operation and the
corresponding values for register 40101 are as follows:
Register 40101 Value
Description
0
Normal operation, current parameter values are copied to “new parameter values” registers each cycle
Remote Client Writes 1
Adapter stops copying current parameter values to “new parameter values” registers each cycle allowing
the remote client to make updates to selected parameters
Remote Client Writes 2
Instructs adapter to write “new parameter values” to CommStat
TM
4 at the next available cycle
Adapter Writes 3
Adapter indicates confirmation of write request and waiting for write cycle completion
Adapter Writes 0
Adapter indicates completion of write to CommStat
TM
4