7.7. 

Configure Alarm Relay 

The alarm relay can be activated at the following events: 
1.  Break In Alarm 

This is used to enable the break in signal of door. if the door is opened by 
other matters except door opening door release button or present card or 
key-in process, the alarm relay will be turned ON and a "alarm occurred" 
signal will be stored in memory of the access controller. 

p.s. The user must enable the Break In Alarm at the Alarm Section in 
Software, and also connect the Door Sensor to the controller. 

2.  Door Open Alarm 

This is used to define the period of door that allows to be opened. The 
period can be set from 1 to 99 second. 0 is disabled this function. If the 
door is opened out of this period, the alarm relay will be turned ON and a 
"alarm occurred" signal will be stored in memory of the access controller. 

p.s. The user must input the time (sec) at the Door Open Alarm field in 
Software, and also connect the Door Sensor to the controller. 

3. Duress Alarm 

If the door is opened with key in the duress pin code, the alarm relay will 
be turned ON and a "alarm occurred" signal will be stored in memory of 
the access controller. 

p.s. The user must enable the Duress Alarm jumper(JP8) in the controller 
in order to activate this function. 

4.  Invalid Card & PIN

 

If the entrance need to input pin code after the card presented, and the 
cardholder key in "WRONG CODE" for 7 times continuously. For security 
reason, the alarm relay will be turned ON and a "alarm occurred" signal 
will be stored in memory of the access controller. 
 

7.8. 

Configure Other EXP-06E Options 

Watch Dog 

For keep looking up the event in the controller.   
Default is Disable (Open) – JP15. 

Duress Alarm  : 

For activate the alarm when keyin the duress pin code.   
Default is Disable (Open) – JP8. 

Chain Ending  : 

For set the controller as the end of the chain 

 

 

 

 

Default is Disable (Open) – JP18. 

12V DC   

For turning ON/OFF the 12V DC input to the controller. 
Default is ON (Short) – JP12. 

5V/12V DC  : 

For choosing 5V/12V DC output for card reader. – JP14 

Summary of Contents for EXP-06E

Page 1: ...Access Control System EXP 06E Single Door Access Controller Installation and Operation Instructions Version 6 6 Revision 2003 5...

Page 2: ...t sensors such as intrusion motion detectors door contacts low temperature and can activate cameras or lighting controls automatically unattended The ACS access Control System provides user with much...

Page 3: ...rsion Motherboard 1 x RS232 port Display SVGA 800x600 resolution color monitor with 16 bits color Input Device Enhanced 101 keyboard and serial mouse Floppy Disk 1 x 3 5 high density floppy disk drive...

Page 4: ...9 Pin Entry Time Zone 3 Cardholder Authority Levels 3 Holidays 100 IN Reader Can be using LED Indication Lamp with Keypad OUT Reader Only LED Indication Lamp System Characteristics Multiple Technolog...

Page 5: ...232 RS485 Converter Modem Modem Telephone Line EXP 06E EXP 06E 1 32 RS232 RS485 Converter EXP 06E EXP 06E 1 32 E E D D D D Communication Configurations E Wire Label From To Function Gauge AWG No of Pa...

Page 6: ...ly 6 3 Single Pin Code Entry Only At this operation mode users can key in the card number through keypad instead of card operation Press key will enable this function if this operation is set If user...

Page 7: ...proximity card reader s LED light will hold on 5 seconds to green color user should release key 0 button in the keypad and key in 4 digits the current used pin code If the key in pin code is correct...

Page 8: ...code is 0001 then the duress pin code should be 0002 i e If the user pin code is 9999 then the duress pin code should be 0000 6 9 Double Pin Code Entry for Duress Pin Code If duress alarm function in...

Page 9: ...l The EXP 06E has two types of battery backup onboard memory and operational power The operational power battery known as the Advanced Power Supply APS gives the EXP 06E internal power fail capability...

Page 10: ...l diode parallel to the door lock 2 ATTENEION It may affect the performance of EXP 06E when diode is not installed parallel to the lock See Figure 1 2 7 3 3 Door Release Button Door Sensor 1 Connect o...

Page 11: ...ommunication using the RS 232C communication using the RS 485 communication protocol set jumpers JP4 JP5 to 1 2 position 7 4 2 RS 232C Connection Table Pin connection EXP 06E Pin Signal DB25 DB9 Host...

Page 12: ...r Model ic485Ip 1F Table Pin connection EXP 06E Pin Converter E 2 4 Sort F 1 3 Sort 7 5 Connection with Advanced Power Supply Option The Power Supply Board provides uninterrupted power backup of EXP 0...

Page 13: ...put the time sec at the Door Open Alarm field in Software and also connect the Door Sensor to the controller 3 Duress Alarm If the door is opened with key in the duress pin code the alarm relay will b...

Page 14: ...1 Memory 32KB Clock Data Memory back up battery Non charge 1 month backup during power failure Communication Interface RS232 and RS485Converter type Data Transfer Rate Local Remote 9 600 bps Input Vol...

Page 15: ...tput Alarm Relay Output IBM Compatible PC KEY PAD JP14 DATA 1 STROBE DATA 0 DATA BEEPER NOT USE CARD PRESENT LED GND VDC RAM Program Chip EXP 06E Controller Board CPU I O 2 I O 1 JP15 JP8 JP18 JP12 CO...

Reviews: