   Hydrocont K 

 

 

page 7 of 16 

 

Electrical connection

 

 

The electrical connection of the device must be carried out according to the respective country specific 

standards. 

Incorrect installation or adjustment could cause applicationally conditioned risks.

 

 

Use only twisted shielded signal and measurement wires and install these wires separated from power leading 

wires. Connect the cable shield only at one side to earth, ideally at the installation place of the device. 

The earthing of the cable shield of an connected cable can be done at the installation place of the connection 

housing by using the terminal PE. At the variant with plug M12x1 the earthing of the cable shield must be done 

at the evaluation side of the installation. 

 

The metallic parts of the device (probe housing, screwing thread of the connection housing) are electrically 

connected with the terminal PE in the connection housing. The socket of the plug M12x1 is not connected to the 

other metallic parts of the device. 

 

The cable gland is suitable für cable diameter from 7 to 13 mm. 

After the installation of the cable the cable gland must be firmly screwed to ensure the tightness of the 

connection housing. The same is valid for the housing cap.

 

 

The voltage applied to the plug contacts may not exceed 45 V

to avoid damage of the electronic.  

All connections are polarity protected.

 

 

A load, e.g. the measuring shunt of an evaluation device, in series with a device with 4...20 mA current signal in 

2-wire-technology reduces the supply voltage available at the device. This results in a maximum value for this 

resistor, where a correct function is still possible. 

 

The maximum load at signal current 20mA can be calculated by the equation: 

 

R

L

 max = (V

S

  – 12,5V) / 20mA  with V

S

 = applying supply voltage.

 

 

For inauguration it is suggested, to deactivate all connected control devices, to avoid unwanted control 

reactions. 

 

connection – non explosive hazardous area 

Power supply 

12,5..45V DC 

evaluation device 

e.g. 

display 

controller 

writer 

 

 

+V

S

 

-V

terminal 1 

 I

Meas

 

terminal 2 

 +V

S

 

terminal 3 

 I

OUT

 (4…20mA) 

 

terminal 4 

 PE/shield

 

4...20mA

 

 

 

 

 

 

 

PE-Anschluss über  

Einschraubgewinde 

 

PE-Anschluss über  

Einschraubgewinde 

PE connection by 

screw in thread

 

connection – explosive hazardous area 

 

4...20mA 

 

Power supply 

12,5..30V DC 

evaluation device 

e.g. 

display 

controller 

writer 

 

 

+V

S

 

-V

isolation barrier 

 

view to  

plug socket 

PE connection by 

screw in thread

 

 

PE-Anschluss über  

Einschraubgewinde 

 

PE-Anschluss über  

Einschraubgewinde 

terminal 1 

 I

Meas

 

terminal 2 

 +V

S

 

terminal 3 

 I

OUT

 (4…20mA) 

 

terminal 4 

 PE/shield

 

 

 

 

 

 

 

PE-Anschluss über  

Einschraubgewinde 

 

PE-Anschluss über  

Einschraubgewinde 

PE connection by 

screw in thread

 

view to 

plug socket 

PE connection by 

screw in thread

 

 

PE-Anschluss über  

Einschraubgewinde 

 

PE-Anschluss über  

Einschraubgewinde 

Summary of Contents for Hydrocont K

Page 1: ...ons Large selection of styles and materials ATEX II 1 2 G Ex ia IIC T4 Ga Gb resp ATEX II 2 G Ex ib IIC T4 Gb Certificated for the use in explosive hazardous areas Integrated evaluation electronic in 2 wire technology with signal 4 20mA Integrated over voltage protection Adjustable measuring signal adjustable signal damping L a u t e r b a c h s t r 5 7 8 4 3 0 7 E g g e n f e l d e n G e r m a n ...

Page 2: ...embrane 4 Safety notes 5 Safety notes 5 Installation 6 Maintenance 6 Repair 6 Electrical connection 7 Operation elements adjustment 8 Technical data 9 10 Dimension drawing 11 12 Order code overview 13 Dimension drawing variant with material PEEK 14 Order code overview variant with material PEEK 15 ...

Page 3: ... of the capacity at the back side of the membrane A pressure transmitting liquid is not used The ceramic membrane offers excellent characteristics like highest pressure and pressure blow strength up to eighty times the nominal pressure vacuum resistance very high resistance against chemicals corrosion and abrasion as well as very good insensitiveness against temperature shocks highest accuracy and...

Page 4: ...1000 mbar 0 barabs 10 barrel 0 2000 mbar 0 barabs 18 barrel 0 4000 mbar 0 barabs 25 barrel 0 10000 mbar 0 barabs 40 barrel 0 20000 mbar 0 barabs 40 barrel 0 25000 mbar 0 barabs 40 barrel 1000 1000 mbar 0 barabs 18 barrel 1000 6000 mbar 0 barabs 40 barrel 0 1000 mbar absolute pressure 0 barabs 10 barabs 0 4000 mbar absolute pressure 0 barabs 25 barabs Permissible pressure to the measuring membrane ...

Page 5: ... conformity certificate must be observed The installation of explosive hazardous systems must be carried out principally by specialist staff The device meets the classification II 1 2 G Ex ia IIC T4 Ga Gb II 2 G Ex ib IIC T4 Ga The devices are conceived for measurement of filling levels in explosive hazardous areas The measured medium may also be combustible liquids gases fogs or steams The permit...

Page 6: ...ake care that the sensor cables that are connected at the bottom side of the electronic module will not be damaged or detached Loosen now the three screws below and rotate the connection head into the desired orientation After that fix the three screws again The electronic module must be inserted now and fixed with the two screws The correct function of the device within the specific technical dat...

Page 7: ...electronic All connections are polarity protected A load e g the measuring shunt of an evaluation device in series with a device with 4 20 mA current signal in 2 wire technology reduces the supply voltage available at the device This results in a maximum value for this resistor where a correct function is still possible The maximum load at signal current 20mA can be calculated by the equation RL m...

Page 8: ...tion of the potentiometer adjustment at zero and end value produces additionally an influence the respectively other value The adjustment range is limited to Maximum zero value increasement to 25 of the nominal measuring range Minimum measuring range 25 of the nominal measuring range Adjustment trimmer damping For adjustment of the damping of the measuring signal For neutralization of short pressu...

Page 9: ...ane diameter Influence of supply voltage 0 01 FS 2 10V Minimum delay time 2 ms at maximum damping 20 seconds damping characteristic exponential Mounting position Maximum deviation 10 0 18 mbar High temperature variant type H At versions with process diaphragm seal the deadweight of the membrane and of the pressure transmitting liquid produces an additional zero value shift whose amount depends on ...

Page 10: ...ere Kalrez others FPM fluorelastomere Viton silicone Environmental conditions Environmental temperature 20 C 85 C limitation at Ex variants Limitation by variant Environmental temperature range Carrying cable 20 70 C Limitation by material Environmental temperature range Connection housing PP 10 85 C Process temperatures 20 C 125 C limitation at Ex variants Limitation Extension by variant Process ...

Page 11: ...Hydrocont K page 11 of 16 Dimension drawing ...

Page 12: ...Hydrocont K page 12 of 16 Dimension drawing ...

Page 13: ...ormerly DIN 16288 without process connection B Nut groove adapter Y others on request Electronic output over voltage protection 1 2 wire technology 4 20 mA without over voltage protection 2 2 wire technology 4 20 mA with over voltage protection not for type Ex0K Measuring range P 0 50 mbar 5 0 10000 mbar 9 0 100 mbar 6 0 20000 mbar 0 0 200 mbar A 0 25000 mbar 1 0 400 mbar 7 1000 1000 mbar 2 0 1000...

Page 14: ...Hydrocont K page 14 of 16 Dimension drawing Variant with material PEEK for aggressive liquids ...

Page 15: ...r 9 0 100 mbar 6 0 20000 mbar 0 0 200 mbar A 0 25000 mbar 1 0 400 mbar 7 1000 1000 mbar 2 0 1000 mbar 8 1000 6000 mbar 3 0 2000 mbar E 0 1000 mbar absolute pressure 4 0 4000 mbar H 0 4000 mbar absolute pressure Y special measuring range separate spec necessary Material connection housing A PP polypropylene C CrNi steel D POM polyoxymethylene Delrin Electrical connection 1 Terminal box 2 Plug M12x1...

Page 16: ...Hydrocont K page 16 of 16 ...

Reviews: