ACS-CONTROL-SYSTEM GmbH

 l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]

12

10

5. Setting up the device

Menu level

Parameterisation level

Function for threshold value undercut / exceedance, 

Fu-1:

Default: 

high

A  limit value undercut is selected with

Louu

(for LOW  =  lower limit value),  a  limit value

exceedance with

High

(for HIGH = higher limit value). If e.g. limit value 1 is on a threshold level

of 100 and allocated with function

High

, an alarm is activated by reaching of the threshold level. 

If the threshold value was  allocated to 

Low,

an  alarm will  be activated by undercutting the

threshold value, as long as the hysteresis is zero. 

The same applies to 

LI-2

!

User code (4-digit number-combination, free available), 

U.CodE

:

Default: 

0000

If this code was set (> 0000), all parameters are locked for the user, if

LOC

has been selected

before under menu item

run

.  By pressing

[P] 

for 3  seconds in  operation mode,  the display

shows

COde

. The

U.Code

needs to be entered to get to the reduced number of parameter sets. 

The code has to be entered befor each parameterisation, until the

A.Code

(Master code) unlocks

all parameters again.

Master code (4-digit number-combination, free available), 

A.CodE

:

Default: 

1234

All parameters can be unlocked with this code, after

LOC

has been activated under menu item

run

. By pressing

[P] 

for 3 seconds in operation mode, the display shows

COde

and enables the

user to  reach all  parametes by entering the

A.codE

.  Under

run

the parameterisation can be

activated permanently by selecting

ULOC

or

ProF

, thus at an anew pushing of 

[P]

in operation

mode, the code needs not to be entered again.

5.3. Programming interlock „

RUN

Activation  /  deactivation  of  the  programming  lock  or  completion  of  the  standard 

parameterisation with change into menu group level (complete function range),

run:

Default: 

uloc

Choose between the deactivated key lock 

Uloc

(works setting) and the activated key lock 

Loc

, or 

the  change  into  the  menu  group  level 

ProF

with  the  navigation  keys 

[

]  [

]

.  Confirm  the 

selection with 

[P]

. After this, the display confirms the settings with 

"

- - - - -"

, and automatically 

switches to operating mode. If 

Loc

was selected, the keyboard is locked. To get back into the 

menu level, press 

[P]

for 3 seconds in operating mode. Now enter the 

CODE

(works setting 

1 2 3 

4

)  that  appears  using 

[

]  [

plus 

[P]

to  unlock  the  keyboard. 

FAIL

appears  if  the  input  is 

wrong. To parameterise further functions

ProF

needs to be set. The device confirms this setting

with

- - - - -

and  changes automatically in  operation mode.  By pressing

[P]

for approx.  3 

seconds in operation mode, the first menu group

InP 

is shown in the display and thus confirms

the change into the extended parameterisation.  It stays activated as  long as 

ULOC

or

LOC

is

entered in menu group

RUN

.

Summary of Contents for DAL-311x9x0S

Page 1: ...Ohm melt pressure sensors Technical features red display of 19999 99999 digits optional green orange or blue display installation depth 120 mm without plug in terminal min max memory 30 parameter driv...

Page 2: ...4V DC 50mA and digital input 1 Y other voltages function input 9 weighing technology function output A display 2 relay outputs changeover B display 4 relay outputs C display with analog output 0 10V 4...

Page 3: ...evice parameters FCT 14 Superior device functions like Hold Tara min max permanent averaging brightness control as well as the control of the digital input and keyboard layout 5 4 3 Safety parameters...

Page 4: ...can be unlocked again by an individual code Optional the following functions are available a 10 V bridge feeding a digital input for the triggering of Hold Tara or the 80 alignment two analog outputs...

Page 5: ...evice 2 Check the seal to make sure it fits securely 3 Click the fixing elements back into place and tighten the clamping screws by hand Then use a screwdriver to tighten them another half a turn CAUT...

Page 6: ...Electrical connection Type M3 1MR5B 020X 470BD supply of 115 VAC Type M3 1MR5B 020X 570BD supply of 230 VAC Type M3 1MR5B 020X 670BD supply of 10 30 VDC DAL 311x9x0S with digital input and external vo...

Page 7: ...ems which are sufficent to set the device into operation are displayed To get into the professional level run through the menu level and parameterise prof under menu item RUN Menu group level complete...

Page 8: ...B interface Software Windows XP Windows VISTA With this tool the device configuration can be generated omitted and saved on the PC The parameters can be changed via the easy to handle program surface...

Page 9: ...V via SEnS F Confirm the selection with P and the display switches back to menu level Setting the end value of the measuring range END Default 10000 Set the end value from the smallest to the highest...

Page 10: ...d then the display changes onto the para meterised display value The same goes for AVG here the sliding average value is displayed If HOLD has been selected the moment can be hold constant by pressing...

Page 11: ...rmed with P A minus sign can only be parameterised on the highest digit After the last digit the device changes back into menu level Setting up the initial value of the analog output Out OF Default 00...

Page 12: ...fter LOC has been activated under menu item run By pressing P for 3 seconds in operation mode the display shows COde and enables the user to reach all parametes by entering the A codE Under run the pa...

Page 13: ...gn can only be parameterized on the highest value digit After the last digit the display switches back to the menu level If Sens was selected as input option you can only select between noca and cal W...

Page 14: ...tion has been selected these parameters are not available Rescaling the measuring input values OFFA Default 0 With this function you can rescale the input value of e g 3 5 mA works setting without app...

Page 15: ...values for setpoints InP 01 InP 30 The setpoints are always set according to the selected input signal The desired analog values can be freely parameterised in ascending order Device undercut dI Und D...

Page 16: ...is for instable display values where the display value is changed in increments of 1 5 10 or 50 This does not affect the resolution of the optional outputs With P the selection is confirmed and the d...

Page 17: ...rolled hold value the sliding average value the constant value or the difference between constant value and current value can be allocated to the display With P the selection is confirmed and the devi...

Page 18: ...connection without consideration of a previous taring If no is selected the navigation keys are without any function in the operation mode Special function O key tASt 4 Default no For the operation m...

Page 19: ...too Functions description see tASt 4 Back to menu group level rEt With P the selection is confirmed and the device changes into menu group level fct Menu level Parameterisation level User code U Code...

Page 20: ...can be changed from e g 0 20 mA to 4 20 mA or 0 10 VDC ALL analog output parameters are released no all analog output parameters are locked Release lock alarm parameters AL LEU Default all This parame...

Page 21: ...dbus transfers no binary cycle but the ASCII Code Thus it is directly readable however the data throughput is smaller in comparison to the RTU Modbus RTU RTU Remote Terminal Unit transfers the data in...

Page 22: ...P the selection is confirmed and the device changes into menu level Selection analog output Out rA Default 4 20 Three output signals are available 0 10 VDC 0 20 mA and 4 20 mA Select the desired signa...

Page 23: ...est or highest possible binary value This means that values of e g 0 mA 0 VDC or values higher than 20 mA or 10 VDC can be reached With P the selection is confirmed and the device changes into menu le...

Page 24: ...ith and confirmed digit per digit with P A minus sign can only be parameterised on the highest digit After the last digit the device changes back into menu level Overflow behaviour Ou2 fl Default edge...

Page 25: ...device changes into menu level Logic relay 1 Log 1 Default or Here the switching behavior of the relay is defined via a logic link the following schema describes these functions with inclusion of AL...

Page 26: ...vior of the relay is defined via a logic link the following schema describes these functions with inclusion of AL 1 and AL 2 This parameter can only be selected if LOGIC was selected under REl 1 A1 v...

Page 27: ...1 Max va in combination with a threshold monitoring Fu 1 High an alarm confirmation can be realised Use the navigation keys or the 4th key for confirmation 5 Setting up the device 25 Menu level Param...

Page 28: ...ected with Louu for LOW lower limit value a limit value exceedance with High for HIGH higher limit value If e g limit value 1 is on a threshold level of 100 and allocated with function High an alarm i...

Page 29: ...ined basic state a reset can be carried out to the default values The following procedure should be used Switch off the power supply Press button P Switch on voltage supply and press P button until is...

Page 30: ...e of the change over Hysteresis Broadness of the window between the switching thresholds Working principle Operating current quiescent current 7 Alarms Relays Operating current By operating current th...

Page 31: ...The interface RS485 is connected via a screened data line with twisted wires Twisted Pair On each end of the bus segment a termination of the bus lines needs to be connected This is neccessary to ensu...

Page 32: ...in 1 measuring cycle min 1s or max by trigger Current measuring range value in per cent For min 1 measuring cycle min 1s or max by trigger For min 1 measuring cycle min 1s or max by trigger Current me...

Page 33: ...Digit height 14 mm Segment colour red optional blue green orange Range of display 19999 to 99999 Setpoints one LED per setpoint Overflow horizontal bars at the top Underflow horizontal bars at the bo...

Page 34: ...toMos outputs 8 normally open NO contacts 30 VDC AC 0 4 A Interface Protocol Modbus with ASCII or RTU protocol RS232 9 600 Baud no parity 8 databit 1 stopbit wire length max 3 m RS485 9 600 Baud no pa...

Page 35: ...suppress any interference with the aid of RC spark extinguishing combinations or free wheeling diodes Keep input output and supply lines separate from one another and do not lay them parallel with eac...

Page 36: ...ignal it is only connected on one side or the input is open Not all of the activated setpoints are para meterised Check if the relevant parameters are adjusted correctly An absolutely incorrect alignm...

Page 37: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 37...

Page 38: ...TROL SYSTEM GmbH Lauterbachstr 57 D 84307 Eggenfelden Tel 49 0 8721 9668 0 Fax 49 0 8721 9668 30 info acs controlsystem de www acs controlsystem de Wir erwarten Ihren Anruf F llstand Pegel Druck Tempe...

Reviews: