6. Reset to factory settings
22
Switching-on delay,
ton-1:
Default:
000
For limit value 1 one can preset a delayed switching-on of 0-100 seconds.
Switching-off delay,
toF-1:
Default:
000
For limit value 1 one can preset a delayed switching-off of 0-100 seconds.
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group level
„–Al1–“
.
Parameterisation level
Menu level
The same applies for
Al2
to
al8
.
Menu group level
Programming interlock,
run
:
Description see page 9, menu level
run
To return the unit to a
defined basic state
, a reset can be carried out to the default values.
The following procedure should be used:
• Switch off the power supply
• Press button
[P]
• Switch on voltage supply and press
[P]-
button until
„- - - - -“
is shown in the display.
With reset, the default values of the program table are loaded and used for subsequent operation. This puts
the unit back to the state in which it was supplied.
Caution! All application-related data are lost.
6. Reset to factory settings