5.1. Switching on
Once the installation is complete, start the device by applying the voltage supply. Before, check once again
that all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (
8 8 8 8 8
) is displayed followed by an
indication of the software type and, after that, also for 1 second the software version. After the starting
sequence, the device switches to operation/display mode.
5.2. Standard parameterisation:
(Flat operation level)
To parameterise the display, press the
[P]-key
in operating mode for 1 second. The display then changes to
the menu level with the first menu item
TYPE
.
5. Setting up the device
5. Setting up the device
Setting the decimal point,
DOt
:
Default:
0.0
The decimal point on the display and the physical unit can be changed with
[
▲
] [
▼
]
. If e.g.
temperature measurement in
°
C is selected, then you can choose between 0
°
C and 0.0
°
C in the
parameterisation level. Confirm with
[P]
, the display then switches back to the menu level
again.
Impedance matching,
dot
:
Default:
0.0
The value for the sensor calibration is selectable from the smallest to the highest digit with
[
▲
][
▼
]
and confirmed with
[P]
. After the last digit the display switches back to the menu level
again. The value calibration for a temperature measurement in
°
C can be adjusted between
-20.0 and +20.0 and in
°
F between -36.0 and +36.0. If the type of the measurement is changed
later, then the value is rounded.
Type of temperature metering
UNIT:
Default:
°c
The temperature can be displayed in
°
C or in
°
F. Confirm the selection with
[P]
and the display
switches back to menu level.
Selection of the input signal,
tYPE:
Default:
4l
Available as measuring input types are 3- and 4-wire-Pt100 signals. Confirm the selection with
[P]
and the display switches back to menu level.
Parameterisation level
Menu level