15
0043H
0046H
Alarm amount 1
INT32
R/W
Calculating factor:0.01
unit
:
yuan
0048H
Alarm amount 2
INT32
R/W
004AH
Credit amount
UINT32
R/W
004CH
New purchase
amount
INT32
R
004EH
Times of power
purchase
UINT16
R
Range of values
(
0~9999
)
004FH
Remaining amount
INT32
R
Calculating factor
:
0.01
0051H
Total purchase
amount
INT32
R
0053H-0056H
Reserved
0057H
Mandatory control
word
UINT16
R/W
0001
:
Override it
0000
:
Forced shutdown
0058H
On off control word
UINT16
R/W
0000
:
Forced closing
0001
:
Forced trip
0059H-0060H
Peak and valley
electricity price
UINT32
×
4
R/W
Calculating factor:0.001
unit
:
yuan
0061H
Current threshold
UINT16
R/W
unit:W
0062H
Operation status
word
UINT16
R/W
0063H
Output mode
UINT16
R/W
0000
:
Level output
0001
:
Pulse output
0064H
Demand
UINT16
R
Calculating factor:0.001
unit:kW
0065H
PA
INT32
R
Calculating factor:0.001
unit:kW
0067H
PB
INT32
R
0069H
PC
INT32
R
006BH
PT
INT32
R
006DH
QA
INT32
R
Calculating factor:0.001
unit:kvar
006FH
QB
INT32
R
0071H
QC
INT32
R
0073H
QT
INT32
R
0075H
SA
INT32
R
Calculating factor:0.001
unit:kVA
0077H
SB
INT32
R
0079H
SC
INT32
R
007BH
ST
INT32
R
007DH
PFA
INT16
R
Calculating factor:0.001
Effective range
(
-1000~1000
)
007EH
PFB
INT16
R
007FH
PFC
INT16
R
0080H
PFT
INT16
R
0081H
Freq
INT16
R
Calculating factor:0.01
0082H-035FH
Reserved