14
DTSY1352
Starting address
Data item name
length
Read /
write
remarks
0000H
Current total
electricity
UINT32
R
Calculating factor0.01
unit:kWh
0002H
Current spike electric
energy
UINT32
R
0004H
Current peak electric
energy
UINT32
R
0006H
Current flat electric
energy
UINT32
R
0008H
Current valley
electric energy
UINT32
R
000AH-000CH
Date
,
time
UINT8
×
6
R/W
Seconds, minutes, days, years
000DH-0027H
Reserved
0028H
First time zone
address
First time zone start
data:day
First time zone start
data:month
……
Fourth time zone
address
Fourth time zone
start data:day
Fourth time zone
start data:month
UINT8
×
12
R/W
Time table number:
01 Corresponds to the first set
02 Corresponds to the second
set
002EH
Voltage of A phase
UINT16
R
Calculating factor:0.1
unit:V
002FH
Voltage of B phase
UINT16
R
0030H
Voltage of C phase
UINT16
R
0031H
Electricity of A phase
UINT16
R
Calculating factor:0.01
unit:A
0032H
Electricity of B phase
UINT16
R
0033H
Electricity of C phase
UINT16
R
0034H
Voltage between A-B
UINT16
R
Calculating factor:0.1
unit:V
0035H
Voltage between C-B
UINT16
R
0036H
Voltage between A-C
UINT16
R
0037H
PTValue
UINT16
R/W
Range of values
(
0~9999
)
0038H
CTValue
UINT16
R/W
Range of values
(
0~9999
)
0039H-003BH
Reserved
003CH
First level code
UINT16
R/W
Range of values
(
0~9999
)
003DH
Secondary code
UINT16
R/W
Range of values
(
0~9999
)
003EH-0042H
Reserved