C
、
D
、
E to block, short circuit, time limit overload, phase break, current imbalance fault,
then block, short circuit, time limit overload, phase break, current imbalance fault any fault occurs,
DO3—— logic diagram output 1 action, output passive signal.
Note :”+” representation and logic ," * " representation or logic.
10.3 Custom communication address
The protector has the function of customizing communication address, which makes
communication reading more convenient and effective.
There are 120 communication addresses for user customization. Address 5000-5119 and
5300-5419, the corresponding data values can be customized. If the value of 5300 is written as
2010, the address 5000 is the same as the address 2010 data.
Example: Suppose the user needs to read and write the original address
2003,2300,2307,2309,2335,2357,2758,2800 frequently. These addresses are not continuous
addresses, each read an address data, need to send a MODBUS read command.
In this case, the efficiency can be improved by customizing the address function: the user can
write the address 5300-5307 as 2003,2300,2307,2309,2335,2357,2758,2800 respectively, so that
the definition of the address 5000-5007, read and write, value range and so on will correspond to
the above address one by one. At this time, the user only needs to send a read command to achieve
all data read and write.
10
、
Examples of ordering
Example: specific model: ARD2M-100/CP
Technical requirements: motor power37KW
Communication protocol:MODBUS RTU protocol
;
PROFIBUS protocol
Auxiliary power:AC 220V