- 57 -
903
Control access
R/W
0-Panel
;
1-Native
;
2-Comm
;
3-Remote
;
4-1 in 3
;
5- 1 in 2
;
6-all
control
word
904
1 in 3 permission
output1
R/W
0- Comm
;
1- Native
;
2- Panel
;
3-Stop
;
4-Remote
the
default is 0
word
905
1 in 3 permission
output2
R/W
0- Comm
;
1- Native
;
2- Panel
;
3-Stop
;
4-Remote
the
default is 1
word
906
1 in 3 permission
output3
R/W
0- Comm
;
1- Native
;
2- Panel
;
3-Stop
;
4-Remote
the
default is 2
word
907
1 in 3 permission
output4
R/W
0- Comm
;
1- Native
;
2- Panel
;
3-Stop
;
4-Remote
the
default is 3
word
908
Start method
R/W
0-Protection
mode,1-manual
mode,2-two-step mode,
3-two-speed mode,
4-star triangle,
5-auto-step-down
word
909
Start1delay
R/W
0.1
~
60.0s
word
910
Recovery voltage
R/W
70
~
95%
word
911
Immediate
restart
time
R/W
0.1
~
10.0s
word
912
Restart delay
R/W
1.0
~
60.0s
word
913
Restart control
R/W
0=Off
,
1=operates on
start 1
,
2= operates on
start 2
word
914
Sway electric time
R/W
0.5
~
300.0s
word
915
Voltage drop
50-90%
≤
Recovery
voltage
916-9
49
Reserve
R
word
Programmabl
e setting
950
DO initial state
setting
R/W
0-Normally on
,
1-
Normally off
;
bit0-bit4
correspond DO1-DO5
word
951
DO1 Definition
R/W
0-No input, 1-start 1,