- 49 -
operation
information
599
Event record clear
W
Write data 0xa5b5
word
System
parameter
600
Current
R
1.6
、
6.3
、
25.0
、
100.0
、
250.0
、
800.0
、
1.0
、
5.0
word
601
Current proportional
factor
R
1
、
10
、
100
602
Operational control
bits
R/W
1-Stop
、
2-Start 1
、
3-
Start 2
、
4-Emergency
stop
、
5-resei
word
603
Restore factory
setting
R/W
Write data 0xFFFF
word
604
Input Mark of
Residual Current
Transformer
R/W
0 not input
,
1 input
word
605
Base Wave Switch
R/W
0 Rms
,
1 Fundament
word
606
Motor type
R/W
0 Common motor, 1
Increased safety motor
word
607
CT Ratio
R/W
1A:1-5000 5A:1-1000
other specifications can
not set CT ratio
word
608
Rated Frequency
R/W
45-70Hz
word
609
Motor rated current
R/W
1A:0.1-5000.0A
5A:0.5-5000.0A
1.6A:0.4-1.6A
6.3A:1.6-6.3A
25A:6.3-25.0A
100A:25.0-100.0A
250A:63.0-250.0A
800A:250.0-800.0A
word
610
Motor rated voltage
R/W
57-1200
word
611
Motor rated Power
R/W
High byte
word
612
R/W
Low byte
word
613
Wiring
R/W
0:1P,1:3P4L
,
2:3P3L
word
614
Back light
R/W
1-30s
,
0:Normally on
word
615
Liquid crystal
contrast
R/W
0
~
100
word
616
Main interface index
R/W
1-7(0-20 can write)
word
617
Language
R/W
0-Chinese
,
1-English
word
618
Current mask value
R/W
0-30
word
619
Password
R/W
0000-9999
620
Analog output setting
R/W
Type:0-Ia,1-Ib,2-Ic,3-Ia
word