The PowerWatch Voltage Disturbance Recorder
8
2007 ACR Systems Inc.
Surge, Sag & Outage Measurement
Model number:
PWV-001
Hot to Neutral
Range:
0 to 200Vrms
Accuracy:
±2Vrms*
Resolution:
1Vrms
Neutral to ground
Range:
3 to 150Vrms
Accuracy:
±2Vrms
Resolution:
1Vrms
Model number:
PWV-002
Hot to Neutral
Range:
0 to 270Vrms
Accuracy:
±4Vrms**
Resolution:
2Vrms
Neutral to ground
Range:
3 to 150Vrms
Accuracy:
±2Vrms
Resolution:
1Vrms
*
sags less than 70V for >1 sec will be reported
as øV
**
sags less than 140V for >1 sec will be reported
as øV
Impulse Measurement
Model number:
PWV-001 & PWV-002
Range
Hot to Neutral:
100 to 2500Vpeak
Neutral to Ground:
50 to 2500Vpeak
Accuracy:
±10% of reading
Resolution: 10V
Width Detection:
1 µsec minimum
Phase Angle
Accuracy:
±1° (20° to 180°, 200° to 360°)
Resolution:
1°
Frequency Measurement
Range:
45 to 65Hz
Accuracy:
±0.1Hz (3 cycles minimum)
Resolution:
0.1Hz
Time Measurement
Events <1 second
Accuracy
Hot to Neutral:
±0.5 cycle*
Summary of Contents for PowerWatch
Page 1: ...2007 ACR Systems Inc Reference Guide IMPORTANT PowerWatch...
Page 3: ...PowerWatch is a Registered Trademark of ACR Systems Inc TRADEMARK NOTICES...
Page 9: ...ACR Systems Inc 2 2007 ACR Systems Inc 2007 ACR Systems Inc...
Page 69: ...PowerWatch Operating Overview 62 2007 ACR Systems Inc 2007 ACR Systems Inc...
Page 87: ......