Device settings / advanced settings
To activate the Device settings, click on the following symbol:
This results in the following window.
Reports and alarms:
If the PUMA is used as a stand-alone device that is not connected to a SCADA system, it is possible to receive
a daily status SMS and alarm SMS in case of an alarms.
For daily status SMS, the following parameter must be used: "Daily status SMS in use" to activate the
function.
"Receivers Phone Number." There is only one user who can receive a status SMS.
"Time of day (in full hours)" you want a status SMS for example 9:00 pm. enter the value 9.
Alarms can be sent to 4 different recipients. You can use SMS or standard dial-up. You must enter a delay
between each alert in the list. For SMS, a typical delay of 60 sec. When using dial-up, it will typically be 300
seconds.
Reverse Comm:
In cases where you do not have an MPLS network and you have the option of having a fixed public IP address
associated with your network connection, you can make PUMA the TCP client and then connect to the
SCADA system. The IP address of the public IP address is entered along with the desired TCP port. The PUMA
will then establish a TCP connection to this address.