RECIRCULATING PIPING DIAGRAM:

WATER

HEATER

C

C

T

T

EXPANSION

TANK

HIGH TEMPERATURE

HOT WATER FIXTURES

LOW TEMPERATURE

HOT WATER FIXTURES

HEAT

TRAP

CONTROL

VALVE

BALANCING

VALVE

LOW TEMP
FIXTURE
RETURN

HIGH TEMP

FIXTURE RETURN

T

C

CHECK VALVE

BALANCING VALVE

TEMP/PRESSURE GAUGE

CIRCULATOR

FLOW DIRECTION

C

SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS
OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOW RATE.
SEE LITERATURE.

COLD

WATER

SUPPLY

TYPICAL CONTINUOUS RECIRCULATION

WATER

HEATER

C

C

T

T

EXPANSION

TANK

HIGH TEMPERATURE

HOT WATER FIXTURES

LOW TEMPERATURE

HOT WATER FIXTURES

HEAT

TRAP

CONTROL

VALVE

BALANCING

VALVE

LOW TEMP
FIXTURE
RETURN

HIGH TEMP

FIXTURE RETURN

T

C

CHECK VALVE

BALANCING VALVE

TEMP/PRESSURE GAUGE

CIRCULATOR

FLOW DIRECTION

C

SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS
OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOW RATE.
SEE LITERATURE.

COLD

WATER

SUPPLY

TYPICAL RECIRCULATION WITH AQUASTAT

ADJUSTABLE
AQUASTAT

NOTE: TO BALANCE THE SYSTEM, BEGIN WITH DIVERTING 80% OF THE 
RETURN WATER TO COLD SIDE OF THE TEMPERING VALVE (20% OF THE 
HOT WATER SOURCE). CONTINUE ADJUSTING UNTIL SYSTEM IS FULLY 
BALANCED.
A HEAT TRAP IS RECOMMENDED IF THE MIXING VALVE IS ABOVE THE 
WATER HEATER.

NOTE: TO BALANCE THE SYSTEM, BEGIN WITH DIVERTING 80% OF THE 
RETURN WATER TO COLD SIDE OF THE TEMPERING VALVE (20% OF THE 
HOT WATER SOURCE). CONTINUE ADJUSTING UNTIL SYSTEM IS FULLY 
BALANCED.
A HEAT TRAP IS RECOMMENDED IF THE MIXING VALVE IS ABOVE THE 
WATER HEATER.

Page 7 of 8

Acorn Controls 

Division of Acorn Engineering Company

®

, A member of Morris Group International

SFST Installation & Operation Manual

Manual #7802-117-000

Date: 09/22/17

Summary of Contents for SFST-T-OT-ITG

Page 1: ...to materials which have been damaged by other causes such as mishandling or improper care or abnormal use The repair or replacement of the defective materials shall constitute the sole remedy of the...

Page 2: ...ture does not exceed 115 F 46 C after installation maintenance or repair Not provided by Acorn 1 Wall anchors screws nuts and washers as required 2 Lead free solder and flux for sealing water connecti...

Page 3: ...f Acorn Engineering Company A member of Morris Group International SFST Installation Operation Manual SFST T OT ITG SFST B OB ITG SFST B OT ITG SFST B OSL ITG 127 8 327 13 330 73 4 197 105 8 270 13 33...

Page 4: ...mber of Morris Group International SFST Installation Operation Manual 41 4 108 16 406 73 4 197 73 4 197 16 406 73 4 197 73 4 197 131 2 343 105 8 270 13 4 44 8 203 145 8 371 131 2 343 73 4 197 73 4 197...

Page 5: ...djust as needed refer to adjustment section below Maximum recommended outlet temperature is 115 F 46 C 1 Loosen locknut Detail A 2 Turn on fixture so temperature can stabilize 3 Using 1 4 allen wrench...

Page 6: ...FROM VALVE HOT OR COLD SUPPLY FAILURE OR SHUTOFFS CLOSED OPEN SHUTOFFS OR RESTORE HOT AND COLD SUPPLIES CHECK VALVE FILTERS BLOCKED WITH DEBRIS CLEAN CHECK VALVES AND FILTERS COLD WATER SUPPLY TYPICA...

Page 7: ...ESSURE GAUGE CIRCULATOR FLOW DIRECTION C SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOW RATE SEE LITERATURE COLD WATER SUPPLY TYPICAL RECIRCULATI...

Page 8: ...FOR REFERENCE 15 ITEM DESCRIPTION ADJUSTMENT STEM LOCK NUT 5 VALVE BONNET 6 BONNET O RING 7 ADJUSTMENT STEM 8 ADJUSTMENT STEM O RING 9 SHUTTLE O RING 10 SHUTTLE 11 ITEM DESCRIPTION 12 THERMOSTATIC MO...

Reviews: