Acorn Engineering SFST-T-OT-ITG Installation, Operation And Maintenance Instructions Download Page 2

 

 

Page 2 of 8

SFST Installation & Operation Manual

You are required to thoroughly read all installation 
instructions and product safety information before 
beginning the installation of this product. 

FAILURE TO READ AND FOLLOW PROPER 
INSTALLATION AND MAINTENANCE 
INSTRUCTIONS MAY RESULT IN PRODUCT 
FAILURE WHICH CAN CAUSE PROPERTY 
DAMAGE, PERSONAL INJURY AND/OR 
DEATH.

Acorn Controls is not responsible for damages 
resulting from improper installation and/or 
maintenance. Installation of this valve shall be in 
accordance with 

Uniform Plumbing Code

.

TO ENSURE ACCURATE AND RELIABLE 
OPERATION OF THIS PRODUCT, IT IS 
ESSENTIAL TO:

Ÿ

Properly design the system to minimize

pressure and temperature variations.

Ÿ

Implement an annual maintenance program

to ensure proper operation and temperature
setting of valve(s).

Ÿ

This valve is factory preset. However, it can

be adjusted. It is the responsibility of the
installer and or facility maintenance personnel
to make sure valve outlet temperature does
not exceed 115°F (46°C) after installation,
maintenance or repair.

(Not provided by Acorn)
1. Wall anchors, screws nuts and washers as

required.

2. Lead free solder and flux for sealing water 

connections.

3. Pipe fittings. 
4. 5/8” wrench and 1/8” Allen wrench.

Flush supply lines of all foreign material such as 

Ÿ

pipe dope, chips or solder prior to connecting to 
mixing valve.

To ensure proper installation, review the Manual 

Ÿ

thoroughly to verify rough-ins before beginning 
any work.

Installation and field adjustment are the 

Ÿ

responsibility of the installer.

Maximum water pressure is 125 psi (8.62 bars). 

Ÿ

Maximum inlet hot water temperature is 180°F 
(82°C). Temperature adjustment range* is 
90°C-115°F (32°C-46°C). Valve assembly must 
be drained prior to being subjected to freezing 
temperatures. Valve includes integral check 
valves.

PRESSURE

DROP

10

(69)

5.7

(21.4)

15

(103)

7

(26.2)

20

(138)

8

(30.2)

30

(207)

9.8

(37)

45

(310)

12

(45.4)

60

(414)

13.8

(52.4)

5

(34)

4

(15)

FLOW RATE

GPM (LPM)

PSID (kPa)

Cv

1.8

*In accordance with ASSE 1070 and ASSE 1069

WARNING:

!

SUPPLIES REQUIRED:

Acorn Controls 

Division of Acorn Engineering Company

®

, A member of Morris Group International

!

IMPORTANT

Manual #7802-117-000

Date: 09/22/17

Summary of Contents for SFST-T-OT-ITG

Page 1: ...to materials which have been damaged by other causes such as mishandling or improper care or abnormal use The repair or replacement of the defective materials shall constitute the sole remedy of the...

Page 2: ...ture does not exceed 115 F 46 C after installation maintenance or repair Not provided by Acorn 1 Wall anchors screws nuts and washers as required 2 Lead free solder and flux for sealing water connecti...

Page 3: ...f Acorn Engineering Company A member of Morris Group International SFST Installation Operation Manual SFST T OT ITG SFST B OB ITG SFST B OT ITG SFST B OSL ITG 127 8 327 13 330 73 4 197 105 8 270 13 33...

Page 4: ...mber of Morris Group International SFST Installation Operation Manual 41 4 108 16 406 73 4 197 73 4 197 16 406 73 4 197 73 4 197 131 2 343 105 8 270 13 4 44 8 203 145 8 371 131 2 343 73 4 197 73 4 197...

Page 5: ...djust as needed refer to adjustment section below Maximum recommended outlet temperature is 115 F 46 C 1 Loosen locknut Detail A 2 Turn on fixture so temperature can stabilize 3 Using 1 4 allen wrench...

Page 6: ...FROM VALVE HOT OR COLD SUPPLY FAILURE OR SHUTOFFS CLOSED OPEN SHUTOFFS OR RESTORE HOT AND COLD SUPPLIES CHECK VALVE FILTERS BLOCKED WITH DEBRIS CLEAN CHECK VALVES AND FILTERS COLD WATER SUPPLY TYPICA...

Page 7: ...ESSURE GAUGE CIRCULATOR FLOW DIRECTION C SELECT FLOW RATE NECESSARY TO ENSURE MIXING VALVE IS OPERATING AT AN ASSE 1017 MINIMUM CERTIFIED FLOW RATE SEE LITERATURE COLD WATER SUPPLY TYPICAL RECIRCULATI...

Page 8: ...FOR REFERENCE 15 ITEM DESCRIPTION ADJUSTMENT STEM LOCK NUT 5 VALVE BONNET 6 BONNET O RING 7 ADJUSTMENT STEM 8 ADJUSTMENT STEM O RING 9 SHUTTLE O RING 10 SHUTTLE 11 ITEM DESCRIPTION 12 THERMOSTATIC MO...