41
PP-32
KOOLMASTER PP-32
REV.01
5.8 HEATER SETTINGS
The PP-32 operates up to eight independent heater stages. A start and
stop temperature is defined for each heating stage. The stop temperature
must be at least 0.5°F (0.3°C) greater than the start temperature for a
given heater and the start temperature cannot be greater than the set
point. The number of heater stages needed and the sensor assignment for
each stage is determined during the installation (see sec. 5.14.3 and
5.14.4). The following diagram shows the operation of an heater stage.
Start and stop temperatures of all heater stages can be set separately
for summer and winter seasons. Refer to sec. 5.2.2 to select the proper
season.
Set the function to
"10. Temp. Settings"
from the main menu using
the navigation buttons. The current set point is displayed.
Press the down-arrow key to select
the start or stop temperature of the
desired heater stage.
Use the adjustment buttons to set
the Start or Stop temperature to the desired value.
Proceed in similar fashion for both winter and summer seasons.
Refer to sec. 5.2.2 to select the proper season.
Set Point: 70.°F
Start/Stop Temp
Heat 4 On 78.0(S)
Heat 4 Off 79.0(S)
ON
ROOM T°
OFF
HEATER
HEATER
TURNS ON
HEATER
TURNS OFF
OPERATION OF HEATER STAGES