Press the down-arrow key to select the Hi alarm limit.
Use the adjustment buttons to set the Hi alarm limit to the desired
value.
Note : If you do not want a relay to be turned off in the case of a low
static pressure alarm, set the Low Alarm limit to "
Off" by
pressing the down-arrow key.
Adjusting High/Low Delays
Set the function to
"21.Alarm Limits"
from the main menu using the
navigation buttons then press the right-arrow key.
Use the navigation buttons to select "
2.Static Pressure"
then press
the right-arrow key.
Press the right-arrow key once again in order to select the
"1.Hi/Lo
limits"
option. The Lo and Hi pressure limits are displayed.
Press the down-arrow key in order
to select the "
Lo Delay
" display.
Use the adjustment buttons to set
the Lo Pressure Alarm Delay to the
desired value.
Press the down-arrow key once again to select the "
Hi Delay
" display.
Use the adjustment buttons to set the Hi Pressure Alarm Delay to
the desired value.
Low Alarm .030WC
Hi Alarm .150WC
Lo Delay 60sec
Hi Delay 300sec