ACME 924738 Installation & Maintenance Instructions Manual Download Page 5

Weather Hood Package (WHP)

See Form 610612 for Assembly Instructions 

Acme’s weather hood is designed to mount directly to the inside flanges 

on the wall box and wall collar assembly. 

For a weather-tight seal, add caulking under the WHP flange before 

installing.  Mount weather hood to the wall box or wall collar using cor-

rosion-resistant fasteners. See Figure 10 and 11.  After installing apply 

caulking around all edges and seams.  Flashing over wall box angles 

and weather hood by others.  

Image above shows the correct fit of the weather hood to a wall box or 

wall collar. The WHP is fastened to the inside breaks of the wall collar/

wall box. Outside removable flanges on wall box or wall collar are for 

mounting to the wall. (Fasteners have been omitted.)

MAINTENANCE

1.  Under normal usage, no spare parts are recommended for one 

year of operation. Motor bearings are prelubricated.  Consult infor-

mation printed on motor for lubrication instructions.

2. 

CAUTION! 

Before proceeding, make sure electrical service to the 

fan is locked in the “

OFF

” position.

3. WINDMILLING:

  Even when the power supply is locked out, fans 

may cause injury or damage if the impeller is subject to “windmilling” 

which is the turning of the impeller and drive components due to 

a draft in the system.  To guard against this hazard, the impeller 

should be secured to physically restrict rotational movement.

4.  Fan inlet and inlet areas to ventilator should be kept clean and free 

from any obstructions.

5.  All fasteners should be checked for tightness each time mainte-

nance checks are preformed prior to restarting the unit.

6.  Inspect all moving parts for damage or rust and clean area.

SET SCREW TIGHTENING SCHEDULE

1.  Before initial operation of the fan, tighten set screws according to 

the procedure outlined below.

2.  After 500 operating hours or three months, whichever comes first, 

tighten set screws to the full recommended torque.

3.  At least once a year, tighten set screws to the full recommended 

torque.

PROCEDURE FOR TIGHTENING 

SET SCREWS IN BEARINGS AND HUBS

One Set Screw Application

Using a torque wrench, tighten the set screw to the torque recommend-

ed in the table shown below.

Two Set Screw Application

1.  Using a torque wrench, tighten one set screw to half of the torque 

recommended in the table shown below.

2.  Tighten the second set screw to the full recommended torque.

3.  Tighten the first set screw to the full recommended torque.

VARIABLE FREQUENCY  

DRIVES AND MOTORS

There are occasions when a Variable Frequency Drive (VFD) will cause 

poor motor performance and possible damage.  To avoid these prob-

lems, the Company recommends the following:

1.  Select compatible motor and VFD inverter; if possible, the motor 

and  the  inverter  should  be  from  the  same  manufacturer  or  at 

least the inverter selected should be recommended by the motor 

manufacturer.

2.  A motor shaft grounding system should be used to prevent motor 

bearing damage from eddy currents.

NOTE:  The Company will not honor motor warranty claims if 

the customer fails to follow these recommendations.

FLASHING BY OTHERS

Page 5

Recommended Tightening Torque for 

Set Screws

Set Screw Diameter

Torque (in-lbs)

#10

35

1/4

80

5/16

126

3/8

240

7/16

384

1/2

744

9/16

1080

5/8

1500

3/4

2580

7/8

3600

1

5400

FIGURE 10

FIGURE 11

Summary of Contents for 924738

Page 1: ...ill not be responsible for damage during storage These suggestions are provided solely as a convenience to the user who shall make his own decision as to whether to use any or all of them INDOOR The ideal storage environment for fans and accessories is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly ma...

Page 2: ...ovide ignition to combustible or flammable materials unless the unit is specifically built for hazardous environments 3 WARNING If gases other than clean air are to be exhausted using the fan then the user bears the responsibility of determin ing that the fan is appropriate and safe for the application 4 Provide a square opening in the wall equal to the outside dimensions of the fan It is preferab...

Page 3: ...ather resistant only they are not weatherproof NOTE Not all sizes in chart are available in all fan models WALL MOUNTED FACE MOUNT Exhaust or Supply R Fans Illustrated is a typical installation when mounting the fan directly to the wall Flashing over damper by others Propeller to damper distance M is important to reduce turbulence and damper flutter which may lead to premature damper failure See F...

Page 4: ...ional support using hanging rods or support from underneath It is preferable to frame in the opening with 2 x 6 material or similar suitable materi al or metal channels adequate for support of the fan The installer provides suitable fasteners hex bolts or lag screws to secure the fan Dampers are designed to reduce drafts prevent entry of for eign material and limit the amount of rain that enters t...

Page 5: ...ainte nance checks are preformed prior to restarting the unit 6 Inspect all moving parts for damage or rust and clean area SET SCREW TIGHTENING SCHEDULE 1 Before initial operation of the fan tighten set screws according to the procedure outlined below 2 After 500 operating hours or three months whichever comes first tighten set screws to the full recommended torque 3 At least once a year tighten s...

Page 6: ...u use arrows to apply fan order speed Brown 0 10VDC to Motor Blue Common White Black Black Black Red Green Yellow Green Handi Box Disconnect Switch Motor Yellow White Yellow White 115 V Red 208 V Orange 230 V Brown 277 V Connect to wire of input voltage and insulate the rest 115 or 208 230 VAC 1 Ph 24 VAC Transformer POWER INPUT LINE ECM MOTOR WIRING FOR GENTEQ MOTORS ONLY USING THE FSC 1 CONTROLL...

Page 7: ...ellow Yellow White Motor Handi Box Disconnect Switch BY OTHERS Green Green Yellow Red Black Black Black White Blue Brown W h i t e A B White Red Black not used Speed control may be mounted up to 100 ft away from fan Hold down center button to access menu Use arrows to navigate apply these settings APPS to 0 10 SP1 too Speed 1 SP2 to Speed 2 tYPE to tC42 rE to 2Spd Once out of menu use arrows to ap...

Page 8: ...by the key to save your changes Programming Please refer to the FSC 1 Menu Map on page 9 for edi ng parameters within program mode To enter program mode hold the key for three seconds un l APPS is displayed Use the and keys to navigate to the desired menu parameter shown in column 1 of the menu map on page 9 To edit a menu parameter press the key once on the desired parameter The current value wil...

Page 9: ...GENTEQ US Motor Page 9 ...

Page 10: ...c fields in the vicinity of current carrying conductors and permanent magnet motors can result in a serious health hazard to persons with cardiac pacemakers metal implants and hearing aids To avoid risk stay away from the area surrounding a permanent magnet motor WARNING Do not remove cover for at least five 5 minutes after AC power is disconnected to allow capacitors to discharge Dangerous voltag...

Page 11: ...s Rotation can be changed by swapping any of the Red Black and Blue wires connecting the control board to the motor at terminals T1 T2 and T3 INSTALLATION 1 Wire motor in accordance with local codes The motor can be mounted by the feet or face See Figure 14 for mounting hole locations Verify fasteners holding motor to fan are properly secured 2 Verify fan wheel is properly secured on motor shaft 3...

Page 12: ...tch will select the Low LO or High HI speed on the speed controllers based on the dial settings Toggle switch and mounting plate fit in a standard gang box and wired to Dual Potentiometer Speed Dial The speed dial can be mounted up to 100 ft from fan using additional wire by others Building Control 0 10VDC Wire Kit See Figure 20 Factory mount ed Molex receptacle that allows a quick connection to s...

Page 13: ...lding Supplied Controller Not Used with Building Supplied Controllers White Green Ground Black N L1 L2 Motor Control Box Line Voltage 208 230 VAC Single Phase 14 AWG Remote Potentiometer A Variable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Speed B Potentiometers mounted up to 100 ft from fan FIGURE 17 FIGURE 18 Page 13 ...

Page 14: ...in that they are secure Fault Indication A red LED on the control board provides fault indication During a fault this LED will blink a specific number of times to identify the fault that has occurred The table below describes these fault indications Maintenance EBSM motors use brushless technology with sealed bearings so no maintenance is required other than keeping any accumulated debris from col...

Page 15: ... potentiometer box Speed B on box is not used for single speed selection and will not have a dial The motor will shut off between 0 1 9V Two Speed Dial See Figure 23 Motor will come with a prewired control cable and wired to a mounted dual speed potentiometer dial that is used to control the speed of the motor The supplied un mounted toggle switch will select the Low LO or High HI speed on the spe...

Page 16: ...peed Potentiometer Speed Select Control A Black Red White Wired in Field B Red to Red White to White Black to Black Potentiometers and speed selector can be mounted up to 100 ft from fan A Variable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Speed B Page 16 FIGURE 24 FIGURE 23 ...

Page 17: ...View PARTS LIST LEGEND No Description Qty No Description Qty 1 Propeller 1 6 Motor Mounting Nuts 4 2 Orifice 1 7 Key 1 3 Frame Assembly 1 8 Frame Mounting Bolts 6 4 Motor 1 9 Frame Mounting Nuts 6 5 Motor Mounting Bolts 4 FIGURE 25 ...

Page 18: ...ely claim the Company shall have the option either to inspect the product while in Purchaser s possession or to request Purchaser to return the product to the Company at Purchaser s expense for inspection by the Company The Company shall replace or at its option repair free of charge any product it determines to be defective and it shall ship the repaired or replacement product to Purchaser F O B ...

Reviews: