Operation

Operating temperature range is: 14°F to 104°F (–10°C to 40°C)

The EBSM motor offers various control options. Follow the correct wir-

ing diagram based on the control option desired.

1.  Energize  motor  and  check  for  proper  rotation.    Rotation  should 

match  wheel  rotation  as  noted  in  fans  instruction  manual  and 

rotation arrow located on fan.

2.  Adjust  motor  speed  to  verify  the  proper  motor  speed  controller 

functionality.

Troubleshooting

Mounted Speed Control Dial

1.  Check voltage to ensure the motor is receiving the correct control 

input.

2.  Check voltage at the remote dial. 24VAC should be present across 

the 24V and COM terminals.  0-10VDC should be present across 

the 0-10V and COM terminals.

3.  Verify all of the connections inside the fan and make certain that 

they are secure.

Fault Indication

A red LED on the control board provides fault indication. During a fault, 

this LED will blink a specific number of times to identify the fault that 

has occurred.

The table below describes these fault indications.

Maintenance

EBSM  motors  use  brushless  technology  with  sealed  bearings  so  no 

maintenance  is  required  other  than  keeping  any  accumulated  debris 

from collecting on the motor.

Building Supplied Controller Harness

White - Common

Red - 0-10 VDC

Page 14

FIGURE 20

Fault Indications

No. Blinks

Indicated Fault

2

Over current

3

Over voltage

4

Under voltage

5

Communication Error

6

Sync Loss

7

Spin Fault

8

3 Sec/60 sec overload

9

Motor over-temperature

Dual Speed Potentiometer

Speed Select Control

A

Black

Red

White

Wired in

Field

B

Red to Red

White to White

Black to Black

Potentiometers and

speed selector can

be mounted up to

100 ft from fan.

A

Variable

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

Speed

B

FIGURE 19

Summary of Contents for 924738

Page 1: ...ill not be responsible for damage during storage These suggestions are provided solely as a convenience to the user who shall make his own decision as to whether to use any or all of them INDOOR The ideal storage environment for fans and accessories is indoors above grade in a low humidity atmosphere which is sealed to prevent the entry of blowing dust rain or snow Temperatures should be evenly ma...

Page 2: ...ovide ignition to combustible or flammable materials unless the unit is specifically built for hazardous environments 3 WARNING If gases other than clean air are to be exhausted using the fan then the user bears the responsibility of determin ing that the fan is appropriate and safe for the application 4 Provide a square opening in the wall equal to the outside dimensions of the fan It is preferab...

Page 3: ...ather resistant only they are not weatherproof NOTE Not all sizes in chart are available in all fan models WALL MOUNTED FACE MOUNT Exhaust or Supply R Fans Illustrated is a typical installation when mounting the fan directly to the wall Flashing over damper by others Propeller to damper distance M is important to reduce turbulence and damper flutter which may lead to premature damper failure See F...

Page 4: ...ional support using hanging rods or support from underneath It is preferable to frame in the opening with 2 x 6 material or similar suitable materi al or metal channels adequate for support of the fan The installer provides suitable fasteners hex bolts or lag screws to secure the fan Dampers are designed to reduce drafts prevent entry of for eign material and limit the amount of rain that enters t...

Page 5: ...ainte nance checks are preformed prior to restarting the unit 6 Inspect all moving parts for damage or rust and clean area SET SCREW TIGHTENING SCHEDULE 1 Before initial operation of the fan tighten set screws according to the procedure outlined below 2 After 500 operating hours or three months whichever comes first tighten set screws to the full recommended torque 3 At least once a year tighten s...

Page 6: ...u use arrows to apply fan order speed Brown 0 10VDC to Motor Blue Common White Black Black Black Red Green Yellow Green Handi Box Disconnect Switch Motor Yellow White Yellow White 115 V Red 208 V Orange 230 V Brown 277 V Connect to wire of input voltage and insulate the rest 115 or 208 230 VAC 1 Ph 24 VAC Transformer POWER INPUT LINE ECM MOTOR WIRING FOR GENTEQ MOTORS ONLY USING THE FSC 1 CONTROLL...

Page 7: ...ellow Yellow White Motor Handi Box Disconnect Switch BY OTHERS Green Green Yellow Red Black Black Black White Blue Brown W h i t e A B White Red Black not used Speed control may be mounted up to 100 ft away from fan Hold down center button to access menu Use arrows to navigate apply these settings APPS to 0 10 SP1 too Speed 1 SP2 to Speed 2 tYPE to tC42 rE to 2Spd Once out of menu use arrows to ap...

Page 8: ...by the key to save your changes Programming Please refer to the FSC 1 Menu Map on page 9 for edi ng parameters within program mode To enter program mode hold the key for three seconds un l APPS is displayed Use the and keys to navigate to the desired menu parameter shown in column 1 of the menu map on page 9 To edit a menu parameter press the key once on the desired parameter The current value wil...

Page 9: ...GENTEQ US Motor Page 9 ...

Page 10: ...c fields in the vicinity of current carrying conductors and permanent magnet motors can result in a serious health hazard to persons with cardiac pacemakers metal implants and hearing aids To avoid risk stay away from the area surrounding a permanent magnet motor WARNING Do not remove cover for at least five 5 minutes after AC power is disconnected to allow capacitors to discharge Dangerous voltag...

Page 11: ...s Rotation can be changed by swapping any of the Red Black and Blue wires connecting the control board to the motor at terminals T1 T2 and T3 INSTALLATION 1 Wire motor in accordance with local codes The motor can be mounted by the feet or face See Figure 14 for mounting hole locations Verify fasteners holding motor to fan are properly secured 2 Verify fan wheel is properly secured on motor shaft 3...

Page 12: ...tch will select the Low LO or High HI speed on the speed controllers based on the dial settings Toggle switch and mounting plate fit in a standard gang box and wired to Dual Potentiometer Speed Dial The speed dial can be mounted up to 100 ft from fan using additional wire by others Building Control 0 10VDC Wire Kit See Figure 20 Factory mount ed Molex receptacle that allows a quick connection to s...

Page 13: ...lding Supplied Controller Not Used with Building Supplied Controllers White Green Ground Black N L1 L2 Motor Control Box Line Voltage 208 230 VAC Single Phase 14 AWG Remote Potentiometer A Variable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Speed B Potentiometers mounted up to 100 ft from fan FIGURE 17 FIGURE 18 Page 13 ...

Page 14: ...in that they are secure Fault Indication A red LED on the control board provides fault indication During a fault this LED will blink a specific number of times to identify the fault that has occurred The table below describes these fault indications Maintenance EBSM motors use brushless technology with sealed bearings so no maintenance is required other than keeping any accumulated debris from col...

Page 15: ... potentiometer box Speed B on box is not used for single speed selection and will not have a dial The motor will shut off between 0 1 9V Two Speed Dial See Figure 23 Motor will come with a prewired control cable and wired to a mounted dual speed potentiometer dial that is used to control the speed of the motor The supplied un mounted toggle switch will select the Low LO or High HI speed on the spe...

Page 16: ...peed Potentiometer Speed Select Control A Black Red White Wired in Field B Red to Red White to White Black to Black Potentiometers and speed selector can be mounted up to 100 ft from fan A Variable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 Speed B Page 16 FIGURE 24 FIGURE 23 ...

Page 17: ...View PARTS LIST LEGEND No Description Qty No Description Qty 1 Propeller 1 6 Motor Mounting Nuts 4 2 Orifice 1 7 Key 1 3 Frame Assembly 1 8 Frame Mounting Bolts 6 4 Motor 1 9 Frame Mounting Nuts 6 5 Motor Mounting Bolts 4 FIGURE 25 ...

Page 18: ...ely claim the Company shall have the option either to inspect the product while in Purchaser s possession or to request Purchaser to return the product to the Company at Purchaser s expense for inspection by the Company The Company shall replace or at its option repair free of charge any product it determines to be defective and it shall ship the repaired or replacement product to Purchaser F O B ...

Reviews: