- 22 -
5.5.9 Relays
Option
The Relays functionality of the transmitter is fixed as follows:
•
Relay 1 – alarm 1
•
Relay 2 – alarm 2
•
Relay 3 – alarm 3
•
Relay 4 – fail alarm
All four relays can be configured as normally energized or normally de-energized. It is
recommended that the Fail Alarm is normally energized and that the Gas Alarms are normally
de-energized to ensure the proper operation during power failure (Fail asserted, Gas Alarms de-
asserted).