-11- 

 

 

DIGITAL INPUT

 

 
The digital input can be used in order  to signal an event in the product. The 
signal must be applied between the 

‘Digital Input’ pins of the M8 connector. 

 
The  voltage  applied  must  not  exceed  24  VDC.  The  product  interprets  any 
voltage between 0V and 1.5V as  a logic level “0”,  and any  voltage  between 
3V  and  24V  as  a  logic  level  “1”.  Between  1.5V  and  3V,  the  state  is 
undetermined. 
 

ALARM CONTACTOR

 

 
The  product  provides  an  alarm  contactor  in  order  to  signal  a  configuration-
defined  event  to  the  user.  The  alarm  uses  ‘Alarm  contactor’  pins  of  the  M8 
connector. 
 
The  contact  is  closed  during  normal  product  operation  and  opens  when  the 
alarm  condition  occurs.  It  opens  as  well  when  the  product  is  powered  off  or 
not in an operational state. 
 
The  alarm  contact  can  switch  60V  maximum  voltage  with  a  current  up  to 
80mA,  and  protected  against  transient  surges.  This  is  a  first  stage  alarm 
contactor  which  must  not  be  used  to  drive  power  directly.  To  carry  out  this 
function,  please  consider  the  use  of  a  power  relay,  as  shown  in  the  picture 
below:  
 

 

Summary of Contents for RailBox 11ac/WiFi 5

Page 1: ...aurez besoin de un PC Windows pour installer le logiciel WaveManager un navigateur internet récent un smartphone Android pour installer l application optionnelle ACKSYS WaveViewer Copyright 2020 par ACKSYS Selon la loi du 11 mars 1957 tout ou partie du présent document ne pourra être reproduit sans le consentement préalable de ACKSYS Avertissement Ce document n est pas contractuel ACKSYS ne garant...

Page 2: ...ble pour alimenter le produit et ainsi protéger le circuit d alimentation en cas de surintensité Ce fusible n est pas intégré dans le produit il devra donc etre installé à l extérieur Le produit n a pas de bouton Marche Arrêt il démarre automatiquement dès la mise sous tension Vérifiez les voyants Power 1 et Power 2 Power 1 s allume si l alimentation 1 ou la source PoE est présente Power 2 s allum...

Page 3: ...ite WEB ACKSYS www acksys fr Sélectionnez votre produit et cliquez sur Configurer Vous pouvez alors configurer son adresse IP afin qu elle soit compatible avec votre réseau ou encore activer le client DHCP 5 L interface WEB de configuration Dans l onglet Produits du tableau de bord Sélectionnez votre référence en cliquant avec le bouton droit de votre souris Cliquez sur Détails ...

Page 4: ...on vous devez choisir l utilisateur root Par défaut il n y a pas de mot de passe Cliquez sur Login pour accéder au menu SETUP a Vous devez activer l interface radio afin de configurer les paramètres Wi Fi b Sur cette page il faut également choisir le pays pour tenir compte de la législation applicable c Enregistrez vos paramètres en cliquant sur Save Apply ...

Page 5: ...nt d accès Client bridge Mesh Les paramètres Wi Fi Mode 802 11 canaux Prendre en compte la législation en vigueur dans votre pays SSID Les paramètres de sécurité WEP WPA WPA PSK WPA2 WPA2 PSK SSID diffusé ou pas Vous trouverez un descriptif complet sur ces modes de fonctionnement dans le manuel d utilisation WaveOS User Guide N oubliez pas d enregistrer vos paramètres en cliquant sur Save Apply à ...

Page 6: ... 168 1 1 Remarque Tant que le bridge n est pas connecté au point d accès le voyant State clignote PROBLEMES ET SOLUTIONS Aucun voyant ne s allume sur le produit Vérifiez la source d alimentation tension courant et son câblage Le voyant d activité du port ETHERNET utilisé est éteint Vérifiez que l appareil distant connecté au produit est allumé Essayez de vous relier à un autre équipement Vérifiez ...

Page 7: ...jusqu au passage du voyant Diag en rouge Relâchez et attendez qu il repasse en vert signalant que le produit a redémarré en configuration usine RESET Un bouton RESET est accessible en retirant la vis du C KEY uniquement celle côté capot Il convient d utiliser un objet pointu non métallique de diamètre inférieur à 2 5mm pour l actionner MONTAGE DU C KEY Le C KEY est une unité de sauvegarde de la co...

Page 8: ...olex permet de monter dans l embase un câble équipé du même système sans le visser Connecteurs Ethernet M12 Deux ports LAN1 et LAN 2 Connecteur M12 8 pôles femelle codage X à visser Nom du signal Pin DA 1 DA 2 DB 3 DB 4 DD 5 DD 6 DC 7 DC 8 Les deux ports Ethernet supportent également la fonction Auto négociation c est à dire qu ils sélectionnent automatiquement la vitesse de transmission 10 Mbps 1...

Page 9: ...ace WiFi 2 sur modèle double radio uniquement Nom du signal Fonction Ant 1 Chaîne RF 1 Ant 2 Chaîne RF 2 Ant 3 Chaîne RF 3 Ant 4 Chaîne RF 4 Les configurations d antennes qu il est possible d utiliser pour les deux interfaces WiFi1 et WiFi2 sont Ant 1 Ant 1 et Ant 2 Ant 1 Ant 2 et Ant 3 Ant 1 Ant 2 Ant 3 et Ant 4 Pour profiter des performances maximales du produit les 4 antennes doivent être conne...

Page 10: ...faillance matérielle Vert Fonctionnement normal Clignotant Le firmware est en cours de chargement ou le produit est mode emergency upgrade car le firmware est corrompu le recharger avec WaveManager LAN 1 LAN 2 Vert Jaune Allumé Liaison Ethernet établie Clignotant Envoi Réception de données Jaune Connexion en 1000 Base T Vert Connexion en 10 or100 Base Tx Éteint Liaison Ethernet non établie C KEY R...

Page 11: ... D ALARME Le produit dispose d un contact pour signaler l apparition d un événement préalablement configuré Les broches Contact d alarme du connecteur M8 sont utilisées à cet effet Ce contact est fermé en fonctionnement normal et s ouvre si la condition d alarme est réalisée ou si le produit est hors tension ou non opérationnel Le contact commute une tension maximum de 60V et un courant de 80mA Il...

Page 12: ...de fixation de la platine sur le support ne sont pas fournies trou oblong 6 5 mm Plan de la platine Dimensions en mm MISE A LA TERRE Il existe 2 possibilités pour relier le produit à la terre 1 Utilisation de la cosse de terre présente sur le côté du produit 2 Ou l utilisation de l insert M6 de la platine WL PLT 1 Nous recommandons pour une mise à la terre efficace d utiliser une tresse métallique...

Page 13: ...ent 40 C à 70 C 40 F à 158 F Température de stockage 40 C à 85 C 40 F à 185 F Bouton Reset Appui court 1 sec à tout moment Reset Appui long 2 sec pendant le fonctionnement Retour aux valeurs d usine en mode emergency upgrade Retour aux valeurs d usine au démarrage Entrée dans le mode emergency upgrade Logiciel Configuration Détection automatique du produit Interface de configuration web avec prote...

Page 14: ... une source PoE 802 3af at type 2 classe 4 connectée sur LAN2 Branchement des modèles non PoE Il convient de choisir un disjoncteur de calibre In 2 fois supérieur au courant nominal In consommé par le RailBox et une section de câble suffisante pour les consommations maximum du produit Par ailleurs le disjoncteur doit avoir une courbe supportant les courants de démarrage de 10In Interface Wi Fi Nom...

Page 15: ...Y Utile pour les topologies daisy chain LAN1 et LAN2 court circuités en cas de panne produit ou panne d alimentation Contact d alarme Type Relais Statique 1 forme A normalement ouvert Tension max 60VDC polarisé protégé contre les surtensions transitoires Courant de charge max 80mA Résistance ON 25 ohms typique 35 ohms max Isolation 1500V Entrée numérique Type Opto isolée Tension max 24VDC protégée...

Page 16: ...2 dBm MCS 9 Soustraire 2 dBm pour avoir la puissance sur le connecteur RF QMA du produit car les valeurs ci dessus sont les valeurs données par le fabricant de la carte radio sur son propre connecteur RF Sensibilité de réception Tolérance 2dB Bande Mode 1 à 4 antennes 2 4 11g 90 dBm 6M 73 dBm 54M 5 11a 91 dBm 6M 74 dBm 54M 2 4 11n HT20 89 dBm MCS 0 66 dBm MCS 8 2 4 11n ac HT40 87 dBm MCS 0 68 dBm ...

Page 17: ...e de radios et options Etant donné que toutes les combinaisons ne sont pas possibles les références à commander sont listées dans trois tables séparées Les références avec cartes 11n et 11ac wave 1 Les reférences avec cartes 11ac wave 2 Les références avec cartes LTE ...

Page 18: ... 18 Page blanche ...

Page 19: ...a PC equipped with Ethernet access to install the WaveManager software a web browser IE compatible an android smartphone if you want to install the optional ACKSYS WaveWiewer App Copyright 2020 by ACKSYS Under the law of March 11 1957 the reproduction in whole or in part of this work by any means whatsoever is prohibited without the prior written consent of ACKSYS Disclaimer This document does not...

Page 20: ...t integrated into the product it must be installed externally The device has no ON OFF switch It turns on automatically when power is applied Check LEDs Power1 and Power2 Power1 LED is ON if POWER1 power supply or PoE source is ON Power2 LED is ON if POWER2 power supply is ON The device has no ON OFF switch It turns on automatically when power is applied Check LED Power Power1 LED is ON if Power1 ...

Page 21: ...Manager found in web site www acksys com Select the device and click on Setup button You can configure the IP address to make it compatible with your network or activate the DHCP client 5 Product WEB Interface from WaveManager In the Products tab of the dashboard Select your device and select your device using the right mouse button And click on Details ...

Page 22: ...o password is required by default click on Login You get now access to the setup pages In the wireless interfaces overview section you must a Enable the Wi Fi radio interface to set up its Wi Fi parameters alternatively you can navigate to change network and services configuration b Select your country in order to enforce applicable regulation rules c Click on Save Apply to validate ...

Page 23: ...erating mode Access point client bridge Wi Fi parameters 802 11 mode radio channel SSID Wi Fi security parameters WEP WPA WPA PSK WPA2 WPA2 PSK SSID broadcast or not You will find a complete description of all modes in the WaveOS user guide Warning Save your settings by clicking Save Apply Otherwise your settings will be lost if the product has to restart FINAL INSTALLATION 6 Install the device Pl...

Page 24: ... 1 verify the answer returned by PC1 Answer from 192 168 1 1 Notice The State LED is flashing until the bridge connects to the AP TROUBLESHOOTING None of the LED indicators turns ON Verify the power supply voltage cabling The relevant LAN led indicator stays OFF Check that the remote device is turned ON Try to connect to another device Use another Ethernet cable The Wi Fi link does not come up Mak...

Page 25: ...ds until Diag goes red Then release it and wait for the Diag LED to turn green again meaning that the product rebooted with its factory settings RESET Reset button is attainable by unscrewing the C KEY only the top screw Use exclusively a 2 5mm diameter plastic sharp object to press the button C KEY REPLACEMENT The C KEY is a storage device used to save and restore the product configuration It sho...

Page 26: ...The ULTRA LOCK feature enables to connect a cable with a simple Plug to create a perfect connection M12 Ethernet connectors Two Ports LAN1 and LAN2 M12 SPEEDCONNEC 8 poles female connector X coded Signal Name Pin DA 1 DA 2 DB 3 DB 4 DD 5 DD 6 DC 7 DC 8 The two Ethernet ports support also self configuring They allow to automatically selecting the transmission speed 10 Base T 100 Base Tx or 1000 Bas...

Page 27: ...onnector female QMA type Wi Fi 2 antennas only for dual radios models Signal name Function Ant 1 RF Chain 1 Ant 2 RF Chain 2 Ant 3 RF Chain 3 Ant 4 RF Chain 4 The antennas configurations for the two WiFi1 and WiFi2 interfaces are Ant 1 Ant 1 and Ant 2 Ant 1 Ant 2 and Ant 3 Ant 1 Ant 2 Ant 3 and Ant 4 To get the full performance of the MIMO 4T 4R technology you must connect the 4 antennas not provi...

Page 28: ... Green Red for more 120s hardware failure Green Ready to use Blinking Firmware in flash is loading Device is in emergency mode because firmware is corrupted Re load firmware with WaveManager LAN 1 LAN 2 Green Yellow On Link on LAN established Flashing Tx Rx activity Yellow connected in 1000 BASE T Green 10 o100 BASE TX Off Link on LAN broken C KEY Red Green Off C KEY in factory state Red The C KEY...

Page 29: ...rovides an alarm contactor in order to signal a configuration defined event to the user The alarm uses Alarm contactor pins of the M8 connector The contact is closed during normal product operation and opens when the alarm condition occurs It opens as well when the product is powered off or not in an operational state The alarm contact can switch 60V maximum voltage with a current up to 80mA and p...

Page 30: ...ews for panel mounting are not included Drawing of the fixing plate All dimensions are given in mm EARTH GROUNDING Firmly connect the device to a suitable earth There are 2 ways to connect the product to the ground 1 Use the earth clamp located on the side of the product 2 If the device is installed on the fixing plate use the M6 threaded insert of the plate For efficient grounding we recommend to...

Page 31: ...torage temperatures ranges 40 C to 85 C 40 F à 185 F Reset button Short push 1 sec anytime Reset Long push 2 sec while operating Restore factory settings while in emergency upgrade mode Restore factory settings at startup enter emergency upgrade Software Device configuration Automatic device discovery tool Built in web based utility for easy configuration from any web browser user password protect...

Page 32: ...it breaker must have a nominal current In compatible with the needed RailBox power twice larger Also the circuit breaker must have a supported inrush current of 10xIn Coding serie P PoE These products must be powered by a PoE 802 3at type 2 class 4 power source connected to LAN2 Wi Fi interface Number of interfaces 1 or 2 Radio mode Support for IEEE 802 11a 802 11b 802 11g 802 11n and 802 11ac Mod...

Page 33: ...ul for daisy chain network topologies Connect LAN1 to LAN2 in case of device or power supply failure Alarm contact Type Solid state relay 1 form A NO Normally Open Max voltage 60VDC not polarized protected against transient over voltage Max load current 80mA ON Resistance 25 ohms typical 35 ohms max Isolation 1500V Digital input Type Opto isolated Tension max 24VDC protected against over voltage I...

Page 34: ... MCS 0 12 dBm MCS 9 Subtract 2 dBm to get the value available at the RF QMA connector of the product values listed above are given by the radio card manufacturer at the connector of the radio card Rx sensitivity input Tolerance 2dB Band Modes 1 to 4 antennas 2 4 11g 90 dBm 6M 73 dBm 54M 5 11a 91 dBm 6M 74 dBm 54M 2 4 11n HT20 89 dBm MCS 0 66 dBm MCS 8 2 4 11n ac HT40 87 dBm MCS 0 68 dBm MCS 7 62 d...

Page 35: ...ENCES The RailBox range is available with multiple radio models and options but all combinations are not all possible Consequently the models with 11ac wave2 or LTE radio are listed in two separate coding tables ...

Page 36: ... 18 BLANK PAGE ...

Reviews: