MOUNTING 

(Continued)

Now fasten and insert (2) screws #8 x 3/4" TEK 
(provided and recommended) through the 
mounting holes in the flange and tighten until 
the unit is held firmly to the duct. Make sure the 
foam pad is tight to the duct to eliminate any 
possible air leaks. Refer to the 

Wiring Instruc-

tions 

(p. 2-3) to make necessary connections. 

Note:

 All enclosures have the foam pad attached. 

For the “DO” (no enclosure), the foam pad is 
included, but not installed. The foam pad must be 
installed prior to mounting.

0.375"

(9.525 mm)

FIGURE 3: 

MOUNTING FOR DIFFERENT CONFIGURATIONS

FIGURE 2: 

DUCT MOUNTING

-PB

-GD

-BB

-4X

-DO

1.51"

(38.25 mm)

1.59"

(40.39 mm)

1.54"

(39.12 mm)

1.54"

(39.12 mm)

3.01"

(76.51 mm)

3.18"

(80.77 mm)

3.08"

(78.23 mm)

3.08"

(78.23 mm)

1.54"

(39.12 mm)

3.08"

(78.23 mm)

WIRING INSTRUCTIONS

Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all 
sensors. Signal wiring must be run separate from low and high voltage wires (24/120/230VAC). All ACI thermis-
tors and RTD temperature sensors are both non-polarity and non-position sensitive. All thermistor type units 
are supplied with (2) flying lead wires, and all RTD’s are supplied with (2) or (3) flying lead wires – see 

FIGURE 

(below). The number of wires needed depends on the application.

THERMISTOR OR

RTD 2WIRE

WIRE NUT

RTD 3WIRE

SAME COLOR WIRES

WIRE NUT

WIRING FROM CONTROLLER

ANALOG INPUT

WIRING FROM CONTROLLER

ANALOG INPUT

3-WIRE RTD WIRING

2-WIRE THERMISTOR or RTD WIRING

FIGURE 4: 

TEMPERATURE WIRING