Installation Instructions AUTOMATION COMPONENTS, INC
I0000658Rev 1 Page 3 of 4 2305 Pleasant View Road
Middleton, Wisconsin 53562
(888) 967-5224
www.workaci.com
Electrical connections
The power supply
has to be connected
to
and
.
is considered as
system ground. If the analogue output is connected to a controller
the same ground
reference has to be used for
the aSENSE
RL unit and for the control system!
Unless
different transformers are used, special precautions need to be taken.
PLEASE NOTE! The same ground reference
has to be used for the
aSENSE RL
unit and for
the control system!
If possible keep the sensor powered up after mounting.
Connect the analogue output before measuring.
Connection
Terminal
Function
Electrical Data
Remarks
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%),
3W
24 VAC/DC-
2W without output
load
See note 1!
Out(1)
Out(2)
Analogue Output 1 (+)
Analogue Output 2 (+)
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,
Same as Output 1
According to positions
of OUT1 and start
point jumpers.
See note 2!
According to positions
of OUT2 and start
point jumpers.
See note 2 and 3!
5
6
7
Normally closed relay
Relay COM
Normally open relay
Contact free relay
minimum load 1mA/5V
rated load
0,5A/125VAC;
1A/24VDC
Triggered by register
Out(3)
8
Not used
Table I. Electrical terminal connections for
aSENSE RL
Note 1:
The ground terminal is used as negative power supply DC input or AC phase ground
(halfwave rectifier). A single transformer may be used for the entire system.
Note 2
:
aSENSE RL can deliver a voltage or a current loop for Out(1) / Out(2). To change between
voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1) and
one for Out(2), so that one output can be a voltage output and the other a current output. Both, voltage
output and current output can have start points 0 % (0-10 VDC or 0-20mA) or 20% (2-10 VDC or 4-
20mA). The same start point is used for both outputs. See the function manual.
Note 3:
Please use voltage outputs for temperature measurements. The accuracy of temperature
measurements is valid only for units configured in voltage outputs mode.
~+
~+