Electrical connections

 

The power supply 

has to be connected

 

to 

 and

 is considered as 

system ground. If the analogue output is connected to a controller 

the same ground 

reference has to be used for

 

the aSENSE

 

RL unit and for the control system!

  Unless 

different transformers are used, special precautions need to be taken.  

 

PLEASE NOTE! The same ground reference 

has to be used for the 

aSENSE RL

 unit and for 

the control system! 

 

If  possible  keep  the  sensor  powered  up  after  mounting. 

Connect the analogue output before measuring. 

 

Connection 

Terminal 

Function 

Electrical Data 

Remarks 

 

 

 

Power (+) 

 

 

Power ground (-) 

24 VAC/DC+  (+-20%), 

3W 

 

24 VAC/DC- 

2W without output 

load 

See note 1! 

Out(1) 

 

 

 

 

Out(2) 

 

 

 

Analogue Output 1 (+) 

 

 

 

 

Analogue Output 2 (+) 

 

 

 

0-10 VDC or 0-20 mA, 

2-10 VDC or  4-20 mA,

 

 

 

 

Same as Output 1 

 

 

 

According to positions 

of OUT1 and start 

point jumpers.

  

See note 2!

 

 

According to positions 

of OUT2 and start 

point jumpers.  

See note 2 and 3!

 

 

 

 

Normally closed relay 

 

Relay COM 

 

Normally open relay 

 

Contact free relay 

minimum load 1mA/5V  

rated load 

0,5A/125VAC; 

1A/24VDC 

 

 

Triggered by register 

Out(3) 

8

 

Not used 

 

 

Table I.  Electrical terminal connections for

 

aSENSE RL

 

 

 

 

Note 1: 

 

The ground terminal is used as negative power supply DC input or AC phase ground 

 

(halfwave rectifier). A single transformer may be used for the entire system.   

 

Note 2

:

 aSENSE RL can deliver a voltage or a current loop for Out(1) / Out(2). To change between 

voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1)  and 

one for Out(2), so that one output can be a voltage output and the other a current output. Both, voltage 

output and current output can have start points 0 % (0-10 VDC or 0-20mA) or 20% (2-10 VDC or 4-

20mA). The same start point is used for both outputs. See the function manual. 

 

Note 3: 

 Please use voltage outputs for temperature measurements. The accuracy of temperature 

measurements is valid only for units configured in voltage outputs mode.  

~+

~+