FIGURE 2: 

WIRING

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 2

Version: 7.0

I0000584

(-)

(+)

    4 - 20mA

Loop Powered

      Signal

(+) 24 Volt Accessory (Option)

(+) Analog Input

(-) Analog, Power and Accessory Common

(+) Power - 24 VDC/VAC @ 50/60Hz

Relay Common

N.O. (Counter-clockwise or DOWN)

N.O. (Clockwise or UP)

To Floating

Point Actuator

Optional Wiring Setup
4 - 20mA Loop Powered Signal

Controlling a Floating Point Actuator

CCW

CW

COM

Floating

Point

Actuator

 24 VAC

or 24VDC

  Power

  Supply

Summary of Contents for AFP Series

Page 1: ... that side of the circuit board to remove Do not flex board Use no tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect or disconnect wiring with power applied When using a shielded cable ground the shield only at the controller end Grounding both ends can cause a ground loop It is recommended you use an isolated UL listed class 2 transformer when powering the unit with 2...

Page 2: ...mA Loop Powered Signal 24 Volt Accessory Option Analog Input Analog Power and Accessory Common Power 24 VDC VAC 50 60Hz Relay Common N O Counter clockwise or DOWN N O Clockwise or UP To Floating Point Actuator Optional Wiring Setup 4 20mA Loop Powered Signal Controlling a Floating Point Actuator CCW CW COM Floating Point Actuator 24 VAC or 24VDC Power Supply ...

Page 3: ... Version 5 Program AFP_0501 hex 90 135 or 180 seconds Switch SW1 1 2 3 4 90 sec Off On 135 sec Off Off 180 sec On Off Relay stays on with 5 of Max or Min input voltage No overshoot on Max or Min input voltage Version 6 Program AFP_0601 hex 18 75 or 360 seconds Switch SW1 1 2 3 4 18 sec Off On 75 sec Off Off 360 sec On Off Version 7 Program AFP_0701 hex 30 60 or 90 seconds Switch SW1 1 2 3 4 30 sec...

Page 4: ...tacts or the output Never place both at the same time Confirm the resistance operation of meter and connect meter only to the corresponding output terminal G terminal is common for both Resistance can be measured now A dead or near dead short should be measured when the output has been placed in the H position Confirm the appropriate LED it lit Contact tech support if the output is not functioning...

Page 5: ...in the voltage modes will be around 10K Ohms and greater If input is shorted contact tech support at ACI If not shorted remove the controller input common and connect power only to AFP NOTE Place meter in voltage mode and measure VAC and VDC from analog input common wire to power supply common If any voltage is measured in DC or AC a ground loop most likely exists Use a separate 24V transformer fo...

Page 6: ...al Blocks 16 1 31 mm2 to 26 AWG 0 129 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C Polyvinyl Chloride PVC SENSOR NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Range Input Current Signal Range Analog Voltage Signal Input Range with Offset Jumper Analog Current Signal Input Range with Offset Jumper Input ...