The LED indicator is lit during program control
PV
(PV Display)
Indicates the Process/Measured value
SV
It is lit when the Setting Value(SV) is being displayed on the
lower display
TIME
MV
SV
(SV/MV/TIME display)
It indicates the Setting Value(SV), Manipulating Value(MV),
or Time(TIME)
(The display content can be changed by the ‘DISP/SELECT’
key)
AL1
It is lit when the Alarm1 output is ‘ON’
COM
(Communication indicator)
It flashes when the controller is in active communication
with a host computer
Program Parameters Setting
Ramp Rate1:
A ramp consists of a slope(linear gradient) and a target setpoint. The control setpoint
increases or decreases at a linear ramp rate from the actual measured value until a
specified target setpoint is reached. The relative positions of the actual measured value
and the target setpoint determine whether the slope of the ramp is positive or negative.
Parameters R1, R2, R3... express the ramping rate in unites per minute(0.01~99.99),
parameters L1, L2, L3... the appropriate target setpoint in display units.
If R1 = END, the program will be ended when the program runs to the slope.
Target Setpoint 1
:
The target value to which the setpoint ramps when the programmer has been placed into
RVN.
Dwell period 1:
In a Dwell period, the target setpoint, which has been attained, remains unchanged for a
fixed period. All the dwell periods are defined by their duration in minutes with
parameters D1, D2, D3...(0~9999). When the program is running, these parameter display
the time remaining in the active dwell period. If the parameter equals zero, the dwell
period is skipped.
When the controller runs in the
PV displaying status:
1). Select the target program pattern number with the
PTN/ key.
2). press
SET/PROG key, the first program parameter appears in the upper display. The
value associated with this parameter will be shown in the lower display.
3). Use
▲
and
▼
key to modify the value.
4). Press the
PAR/SET key, the next parameter appears. At the same time, the
modification has been saved in the memory. Use
▲
and
▼
key to modify the value.
Repeat this procedure till all the parameters are set. Or if there is no key operation within
16 seconds, the menu times out automatically.