Installation & Operation Manual - Model AV3000 

Contents of this Manual are Subject to Change Without Notification 

Page 17 

 

9.1.1 Rectangular Valve Access Cover 
Equipment Required:

  5/16

” socket with ratchet drive or power driver, 

safety glasses

 

and 

safety gloves

 suitable for sheet metal working. 

 

 
1.  The access cover is secured to the valve using (12) Tek-Screws.  Remove the (12) 

Tek-

Screws using a 5/16” socket and put the screws aside for reinstalling the cover 

later. 

 

 
2.  Remove the access cover from the valve. 
 

 

 
 
3.  Once the cover is removed the sensors are accessible for inspection. 
 
 
4.  When inspection is complete, place the access cover in position and secure using 

the (12) screws previously removed. 

 

 

Access Cover 

Remove (12) Screws 

Inspect Sensors 

Summary of Contents for AccuValve AV3000

Page 1: ...of this Manual are Subject to Change Without Notification Airflow Control Valve Patented U S 6 991 177 7 543 759 Manufactured by Accutrol Representative AV3000 MANUAL ACCUTROL JANUARY 2019 ECN 2433 2...

Page 2: ...s against defects or damages arising from improper installation where installation is by persons other than Manufacturer against defects in products or components not manufactured by Manufacturer or a...

Page 3: ...NTENTS iii SECTION 1 INTRODUCTION 1 SECTION 2 SPECIFICATIONS 3 SECTION 3 MODEL CODE DESCRIPTION 4 SECTION 4 PHYSICAL DIMENSIONS WEIGHTS 5 SECTION 5 INSTALLATION 6 SECTION 6 WIRING 9 SECTION 7 OUTPUT C...

Page 4: ...and compresses creating a laminar zone optimum for measuring airflow velocity The vortex shedding airflow sensors provide a digital pulse train to the airflow transmitter which is directly proportiona...

Page 5: ...3 2 AV3200 36 and 48 Dual Valves Airflow Transmitter Actuator 1 Electric Actuator Access Cover Drive Shaft Airflow Transmitter Housing Actuator 2 Mounting Supports Valve 2 Valve 1 Airflow Inlet View...

Page 6: ...ax differential pressure across valve ENVIRONMENTAL Temperature Air stream 20 to 140 deg F Ambient 25 to 125 deg F Humidity 0 to 95 RH non condensing TRANSMITTER ELECTRICAL Input Power 24 VAC 20 50 60...

Page 7: ...10v Belimo NMQB24 MFT B FLP 4 Fail Open Closed 0 10v Belimo NKQ24 MFT A FSP 5 Fail Open Closed 2 10v Belimo NKQ24 MFT B FSP SIZE 06 6 Diameter 08 8 Diameter 10 10 Diameter 12 12 Diameter 14 14 Diamete...

Page 8: ...6 7 3 AV3100 10 9 88 250 24 610 15 381 20 9 1 AV3100 12 11 88 300 27 686 17 432 26 11 8 AV3100 14 13 88 350 30 762 19 483 30 13 6 4 2 Rectangular Sizes Valve Model W L H Weight in mm in mm in mm lbs k...

Page 9: ...and valve access cover 5 To support the weight of the valve install duct hangers within 12 inches 305 mm of valve connections NOTE Reference Section 4 for valve weights 6 After the duct section is pr...

Page 10: ...Change Without Notification Page 7 Round Valve Installation Standard Slip Fit Valve Using Draw Band Round Valve Installation Option F Flanges 3 8 bolts lock washers and nuts 14 356mm Minimum Clearanc...

Page 11: ...ts 14 356mm Minimum Clearance Rectangular Valve Installation Option F Flanges Additional Requirements for Installing 12X36 and 12x48 Valves All dual valves 12x36 and 12x48 are provided with an integra...

Page 12: ...a 875 22 2mm conduit fitting 6 1 3 Land the wires to the appropriate terminals secure screws and reinstall plugs NOTE Reference job specific wiring diagrams for details of connections to field devices...

Page 13: ...troller Tek Air FVC Controller I P Out I P Out 24 VAC Black Power Signal Common Red 24V Power Input White Ctrl Signal In 2 to 10V Actuator X4 Pin 2 Common X4 Pin 1 Power Input X2 Pin 1 Output Signal 2...

Page 14: ...irect Input Board Signal 2 10 Power 15v Common Cable Shown Below 20 AWG 3 Conductor Shielded Plenum Windy City Wire 003330 AccuValve Model AV3000 RED WHITE BLACK RED WHITE BLACK 6 3 4 Typical wiring b...

Page 15: ...has been configured to provide either Voltage 0 10v or 2 10v or Current 0 20mA or 4 20mA by using Jumpers JP1 and JP4 The factory default transmitter output is 2 10v unless specified otherwise at the...

Page 16: ...Fume Hood Controller Applications All FVC2000 applications utilizing the AV3000 must use the AccuValve Direct input board to connect the AV3000 to the FVC controller If the Fume Hood Controller does n...

Page 17: ...cuValve Direct Input Board the transmitter output jumpers must be configured for 2 10 v operation and the Transmitter Full Scale Range must remain set to the factory default values as shown below Valv...

Page 18: ...ransmitter to which it is connected If it is necessary to adjust the airflow calibration in the field the Vortek Coef Span FPM parameter can be modified 8 5 SmartLab Controller Configuration Standard...

Page 19: ...ugh to allow the access door to slide forward CAUTION If the bolt is removed from the captive nut the access cover can spring open possibly causing injury 2 Using two hands squeeze the access cover an...

Page 20: ...for sheet metal working 1 The access cover is secured to the valve using 12 Tek Screws Remove the 12 Tek Screws using a 5 16 socket and put the screws aside for reinstalling the cover later 2 Remove...

Page 21: ...Installation Operation Manual Model AV3000 Contents of this Manual are Subject to Change Without Notification A APPENDIX A ACTUATOR TECHNICAL DATA SHEETS...

Page 22: ...ed Shut off Leakage specification Revised Operating Range Table Revision Date Jan 2012 New Filename AV3000 MANUAL ACCUTROL JAN 2012 Section Description of Change Cover Revised pictures and revised fil...

Reviews: