Installation & Operation Manual - Model AV3000
Contents of this Manual are Subject to Change Without Notification
Page 12
SECTION 7
– OUTPUT CONFIGURATION
Each AccuValve
®
is tested and calibrated in the factory and performance is verified to
ensure accuracy. The transmitter Full Scale Range is set per the table in Section 2 and
the Analog Output Signal has been configured to provide either Voltage (0-10v or 2-10v)
or Current (0-20mA or 4-20mA) by using Jumpers JP1 and JP4. The factory default
transmitter output is 2-10v unless specified otherwise at the time of placing order.
If desired, the Output Signal can be reconfigured in the field by setting Jumpers
JP1
and
JP4
as shown below.
Desired
Output
Signal
Jumper
Positions
JP4
JP1
4 to 20mA
2-3
OFF
2 to 10 v
1-2
OFF
0 to 20mA
2-3
ON
0 to 10 v
1-2
ON
AV3000 Transmitter
Transmitter pictured is
configured for 2-10v
output: JP4 is set 1-2
and JP1 is OFF.