Upblast Centrifugal Roof Exhaust

6

Grease Trap Installation

The polypropylene grease trap is designed to collect 
grease residue and avoid drainage onto roof surface. 
Follow all local codes, as well as the National Fire 
Protection Agency (NFPA) where applicable.

NFPA 96:

 

Upblast fans shall have a drain directed to a 

readily accessible and visible grease receptacle not to 
exceed 1 gal. 

(3.8L)

Refer to Document 476370

 - Grease Trap Installation, 

Operation and Maintenance Manual for parts list and 
specific installation instructions.

Grease Trap Maintenance

Regular inspection of grease trap is recommended. 
Depending on the amount of grease discharged through 
the fan, the grease trap should be cleaned regularly to 
ensure proper operation.

•  Check grease absorber (if included) every month. 

Replace grease absorber after every cleaning and/
or as needed between cleanings.

•  Replacement grease absorbers (P/N 476084) can 

be ordered from your local representative.

Hinge Installation

NFPA 96:

 Upblast exhaust fans shall be supplied with a 

hinge.

Refer to listed Installation, Operation and 
Maintenance Manuals

 for parts list and specific 

installation instructions:

Document 481937

 - 

Sidewall Mount Hinge Kit

 

Document 481366

 - 

Bracket Hinge Kit

 

 

Document 462865/462866 

Hinge Kit 

Fan to Curb Mounting:  

5/16-inch 

(7.9 mm)

 self-drilling 

fasteners are to be installed on each side of fan with 
one fastener 4-inches 

(102 mm)

 from each edge and 

one fastener in the center, Figure 9. Fasteners are to be 
equally spaced. 

Mounting for Severe Duty Installation

Optional Hinged Base Mounting:  

For installations 

that include the optional hinged base accessory, the 
fan must be secured to the hinged base and curb using 
the correct number of fasteners as shown in the “Fan to 
Curb Mounting” section. All fasteners must be installed 
through the curb cap of the fan, the hinged base, and 
the curb. All fasteners must be reinstalled after each 
time the fan is hinged open, see Figure 10.

IMPORTANT

Only qualified installers should perform this work. 
Manufacturer assumes no liability for damages 
resulting from installation.

Installation instructions for seismic ratings are only 
recommendations. Final design must be determined 
by Structural Engineer of Record (SEOR) including 
requirements for curb construction, mounting of unit 
to curb and mounting of curb to structure.

Fan Size

Fasteners  

per Side 

≤ 161

3

180 to 240

5

≥ 300

9

Unit

1¼ in.

1¼ in. 

Curb Corner

Anchor Detail

Roof Curb
Model GPF, GPFHL, 
GPFHD or Equivalent
18 ga. min.

High Wind Ratings 
42 in. Tall Max

Seismic Ratings
24 in. Tall Max
Welded Steel Construction

Figure 9 - Fan to Curb Mounting

All fasteners 
must penetrate 
curb and must 
be reinstalled 
after each 
service.

Figure 10 - Fasteners

Summary of Contents for XRUB Belt Drive

Page 1: ...icals Replace cord immediately if damaged 6 Verify that the power source is compatible with the equipment Direct Drive Upblast Centrifugal Exhaust Fan These fans are specifically designed for roof and wall mounted applications The maximum continuous operating temperature for fan sizes 099 300 is 400 F 204 C and for fan sizes 060 095 is 130 F 54 C Direct drive fans are available with nominal wheel d...

Page 2: ...oid lifting fans in a way that will bend or distort fan parts Never pass slings or timbers through the venturi of fan Fans with special coatings or paints must be protected in handling to prevent damage 4 Drive Frame Lifting Points 2 Bearing Plate Lifting Points Hook With Safety Latch Supplied by others Figure 2 Screw Screw Figure 3 Figure 1 Handling Direct and Belt Drive Units Lift Direct Drive u...

Page 3: ...isture proof paper or polyethylene sheathing Aisles between parts and along all walls should be provided to permit air circulation and space for inspection IMPORTANT Installation troubleshooting and parts replacement are to be performed only by qualified personnel Consult and follow all applicable national state and local codes They will supercede this document Outdoor Fans designed for outdoor ap...

Page 4: ...terial 6 Verify power line wiring is de energized before connecting fan motor to power source 7 For commercial kitchen and UL Listed emergency smoke control applications the electrical supply must enter the motor compartment through the breather tube For other non flammable applications the electrical supply can be routed through the conduit chase between the curb cap and the bottom of the motor co...

Page 5: ...er DO NOT install it Perform steps 3 12 of General Ventilation Installation IMPORTANT The size of the duct must be equal to or larger than the inlet opening of the fan To comply with NFPA 96 the fan discharge must be a minimum of 40 in 1016 mm above the roof surface and a minimum of 10 ft 3048 mm from any building air intake Per NFPA 96 ductwork to an upblast discharge exhaust fan must be construc...

Page 6: ... Hinge Kit Fan to Curb Mounting 5 16 inch 7 9 mm self drilling fasteners are to be installed on each side of fan with one fastener 4 inches 102 mm from each edge and one fastener in the center Figure 9 Fasteners are to be equally spaced Mounting for Severe Duty Installation Optional Hinged Base Mounting For installations that include the optional hinged base accessory the fan must be secured to th...

Page 7: ...NT La turbine doit impérativement tourner dans le bon sens Une rotation en sens inverse entraînerait de mauvaises performances de soufflage une surcharge du moteur voire un grillage du moteur CORRECT WRONG WRONG WRONG Figure 15 Belt Drive Pre Starting Belt Tension Checks 4 Always loosen tension enough to install belts without stretching Do not force belt s see Figure 14 Forcing belts will break th...

Page 8: ... system in full operation and all ductwork attached measure current input to the motor and compare with the nameplate rating to determine if the motor is operating under safe load conditions 6 Keep inlets and approaches to fan clean and free from obstruction IMPORTANT Adjust tighten belt tension after the first 24 48 hours of operation 9 The adjustable motor pulley is factory set for the RPM speci...

Page 9: ...gn the unthreaded holes of the hub with the threaded holes of the tapered bushing Reverse Mounting Slide the wheel and hub assembly onto the fan shaft followed by the bushing and shaft key If present use the keyway setscrew to hold the shaft key and bushing in place but DO NOT overtighten as this can damage the bushing Align the unthreaded holes of the tapered bushing with the threaded holes of th...

Page 10: ...can be classified in two groups relubricating and non relubricating All non relubricating bearings on belt drive fans are factory lubricated and require no further lubrication under normal use between 20º to 180ºF 29º to 82ºC in a relatively clean environment 8 On belt drive fans the standard cast pillow block bearings are factory lubricated and are provided with external grease fittings Annual lubr...

Page 11: ...ey Drive Frame Assembly Vibration Isolators Vertical Support Windband Wheel Breather Tube Birdguard in tube Hoodband Disconnect Switch Hoodband Bracket Horizontal Support Belt Drive Direct Drive Curb Cap Venturi Wheel Vibration Isolators Motor Hoodband Conduit Chase Horizontal Support Vertical Support Hood Clip Motor Cover Birdguard Breather Tube Motor Support Pan Disconnect Drain Trough Windband ...

Page 12: ...e ductwork Check proper operation of face and bypass dampers Check filters and access doors Fan does not operate Electrical supply Check fuses circuit breakers Check for switches off Check for correct supply voltage Drive Check for broken belts Tighten loose pulleys or belts Motor Ensure motor is correct horsepower and not tripping overload protector Motor overloads or overheats Lubrication Check ...

Reviews: