background image

474737 • XRUD and XRUB, Rev. 11, November 2018 

2018 © Accurex, LLC

12

Our Commitment

As a result of our commitment to continuous improvement, Accurex reserves the right to change specifications 
without notice.

Product warranties can be found online at accurex.com, either on the specific product page or in the Warranty 
section of the website at Accurex.com/Resources/Warranty.

Our Commitment

P.O. Box 410  Schofield, WI 54476
Phone: 800.333.1400 • Fax: 715.241.6191
Parts: 800.355.5354 • accurex.com

PROBLEM

CAUSE

CORRECTIVE ACTION

Excessive 
noise
or vibration

Wheel rubbing inlet

Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.

V-belt drive

Tighten pulleys on motor/fan shaft. Adjust belt tension. Align pulleys properly,  
see page 7, Figures 14 and 15. Replace worn belts or pulleys.

Bearings

Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.

Wheel unbalance

Clean all dirt off wheel. Check wheel balance, rebalance in place if necessary.

Belts too tight or too loose

Adjust tension, see page 8, Figures 17a and 17b.

Wheel improperly aligned and rubbing

Center wheel on inlet, see page 7, Figure 12.

Loose drive or motor pulleys

Align and tighten. See “Pre-Starting Checks”, pages 7 and 8.

Foreign objects in wheel or housing

Remove objects, check for damage or unbalance.

Fan base not securely anchored

Secure properly.

Motor hood loose and rattling

Tighten fasteners to secure the motor hood.

Defective or loose motor bearings

Replace motor with same frame size, RPM-HP

High  
horsepower

Fan

Check rotation of wheel, see page 7, Figure 13. Reduce fan speed.

Duct system

Resize ductwork. Check proper operation of face and bypass dampers.  
Check filters and access doors.

Fan does
not operate

Electrical supply

Check fuses/circuit breakers. Check for switches off. Check for correct supply voltage.

Drive

Check for broken belts. Tighten loose pulleys or belts.

Motor

Ensure motor is correct horsepower and not tripping overload protector.

Motor  
overloads
or overheats

Lubrication

Check for excessive or insufficient grease in the bearing.

Mechanical

Replace damaged bearing. Relieve excessive belt tension. Align bearings.  
Check for bent shaft.

Belt slippage

Adjust tension or replace bad belts, see pages 7 and 8.

Over/Under line voltage

Contact power company.

Incorrect wheel rotation

Check motor wiring, see page 4, Figure 6. Confirm wheel rotation, see page 7, Figure 13.

Wheel RPM too high

Check drives or slow down fan by opening variable pitch pulley on motor shaft.

Undersized motor

Check motor ratings with catalog speed and air capacity chart.

Motor wired incorrectly

Check motor wiring to wiring diagram located on fan motor.

Reduced  
airflow

System resistance too high

Check system: Proper operation of backdraft or control dampers, obstruction in 
ductwork, clean dirty filters.

Unit running backwards

Correct as shown see page 7, Figure 13.

Excessive dirt buildup on wheels

Clean wheel, see page 7.

Improper wheel alignment

Center wheel on inlet, see “Pre-Starting Checks”.

Dampers closed

Inspect and repair.

Blocked duct/clogged filter

Clean or replace.

Belt slippage 

Replace and adjust tension.

Speed too slow

Check for correct drives.

WARNING

Before taking any corrective action, make certain unit 
is not capable of operation during repairs.

AVERTISSEMENT

Avant d’entreprendre toute action corrective, s’assurer 
que l’appareil ne pourra pas fonctionner durant les 
réparations.

Troubleshooting

Summary of Contents for XRUB Belt Drive

Page 1: ...icals Replace cord immediately if damaged 6 Verify that the power source is compatible with the equipment Direct Drive Upblast Centrifugal Exhaust Fan These fans are specifically designed for roof and wall mounted applications The maximum continuous operating temperature for fan sizes 099 300 is 400 F 204 C and for fan sizes 060 095 is 130 F 54 C Direct drive fans are available with nominal wheel d...

Page 2: ...oid lifting fans in a way that will bend or distort fan parts Never pass slings or timbers through the venturi of fan Fans with special coatings or paints must be protected in handling to prevent damage 4 Drive Frame Lifting Points 2 Bearing Plate Lifting Points Hook With Safety Latch Supplied by others Figure 2 Screw Screw Figure 3 Figure 1 Handling Direct and Belt Drive Units Lift Direct Drive u...

Page 3: ...isture proof paper or polyethylene sheathing Aisles between parts and along all walls should be provided to permit air circulation and space for inspection IMPORTANT Installation troubleshooting and parts replacement are to be performed only by qualified personnel Consult and follow all applicable national state and local codes They will supercede this document Outdoor Fans designed for outdoor ap...

Page 4: ...terial 6 Verify power line wiring is de energized before connecting fan motor to power source 7 For commercial kitchen and UL Listed emergency smoke control applications the electrical supply must enter the motor compartment through the breather tube For other non flammable applications the electrical supply can be routed through the conduit chase between the curb cap and the bottom of the motor co...

Page 5: ...er DO NOT install it Perform steps 3 12 of General Ventilation Installation IMPORTANT The size of the duct must be equal to or larger than the inlet opening of the fan To comply with NFPA 96 the fan discharge must be a minimum of 40 in 1016 mm above the roof surface and a minimum of 10 ft 3048 mm from any building air intake Per NFPA 96 ductwork to an upblast discharge exhaust fan must be construc...

Page 6: ... Hinge Kit Fan to Curb Mounting 5 16 inch 7 9 mm self drilling fasteners are to be installed on each side of fan with one fastener 4 inches 102 mm from each edge and one fastener in the center Figure 9 Fasteners are to be equally spaced Mounting for Severe Duty Installation Optional Hinged Base Mounting For installations that include the optional hinged base accessory the fan must be secured to th...

Page 7: ...NT La turbine doit impérativement tourner dans le bon sens Une rotation en sens inverse entraînerait de mauvaises performances de soufflage une surcharge du moteur voire un grillage du moteur CORRECT WRONG WRONG WRONG Figure 15 Belt Drive Pre Starting Belt Tension Checks 4 Always loosen tension enough to install belts without stretching Do not force belt s see Figure 14 Forcing belts will break th...

Page 8: ... system in full operation and all ductwork attached measure current input to the motor and compare with the nameplate rating to determine if the motor is operating under safe load conditions 6 Keep inlets and approaches to fan clean and free from obstruction IMPORTANT Adjust tighten belt tension after the first 24 48 hours of operation 9 The adjustable motor pulley is factory set for the RPM speci...

Page 9: ...gn the unthreaded holes of the hub with the threaded holes of the tapered bushing Reverse Mounting Slide the wheel and hub assembly onto the fan shaft followed by the bushing and shaft key If present use the keyway setscrew to hold the shaft key and bushing in place but DO NOT overtighten as this can damage the bushing Align the unthreaded holes of the tapered bushing with the threaded holes of th...

Page 10: ...can be classified in two groups relubricating and non relubricating All non relubricating bearings on belt drive fans are factory lubricated and require no further lubrication under normal use between 20º to 180ºF 29º to 82ºC in a relatively clean environment 8 On belt drive fans the standard cast pillow block bearings are factory lubricated and are provided with external grease fittings Annual lubr...

Page 11: ...ey Drive Frame Assembly Vibration Isolators Vertical Support Windband Wheel Breather Tube Birdguard in tube Hoodband Disconnect Switch Hoodband Bracket Horizontal Support Belt Drive Direct Drive Curb Cap Venturi Wheel Vibration Isolators Motor Hoodband Conduit Chase Horizontal Support Vertical Support Hood Clip Motor Cover Birdguard Breather Tube Motor Support Pan Disconnect Drain Trough Windband ...

Page 12: ...e ductwork Check proper operation of face and bypass dampers Check filters and access doors Fan does not operate Electrical supply Check fuses circuit breakers Check for switches off Check for correct supply voltage Drive Check for broken belts Tighten loose pulleys or belts Motor Ensure motor is correct horsepower and not tripping overload protector Motor overloads or overheats Lubrication Check ...

Reviews: