![AccuEnergy Acuvim-L Series Quick Setup Manual Download Page 12](http://html1.mh-extra.com/html/accuenergy/acuvim-l-series/acuvim-l-series_quick-setup-manual_3760134012.webp)
Power Supply
Power supply
100~415Vac, 50/60Hz; 100~300Vdc
Power consumption
3W@230Vac
Withstand
3250Vac, 50/60Hz 1min
Altitude
2000m
24DC Auxiliary Power Supply
Operating Range
24Vdc
Nominal consumption
1W
Isolation voltage
1000V
Voltage Input
Nominal Full Scale
400LN/690LL Vac RMS (3-phase)
400LN Vac RMS (single-phase)
With 20% overage (3LN or 2LN wiring)
Installation Category III, Pollution Degree 2
Metering Frequency
45~65Hz
Overload
2 times(continuously); 2500Vac per second (no recurrence)
Voltage range through PT
1000KV highest at primary side
PT burden
<0.2VA
Measuring
True-Rms
Accuenergy Corporation
Los Angeles-Toronto-Beijing
North America Toll Free: 1-877-721-8908
Web: www.accuenergy.com
Document#1030E3301 Revision Date: Nov., 2015
Specification
Current Inputs
Current rating
5Amp AC (1Amp AC Optional)
Current range
50000A highest at primary side
Overload
10A
CT
Burden
Measuring
True-Rms