In the basic parameter setting mode, by setting the correct meter address, 

communication baud rate and parity (Acuvim-CL/DL/EL/KL only), we can 

engage in normal communication.  The connection mode by setting the voltage, 

current connection mode, the voltage transformation ratio PT1, PT2, the voltage 

transformation ratio CT1, CT2 in order to achieve accurate measurement of the basic 

amount.  Please refer to the specific setting 

"Acuvim-L User's Manual"

.

Communication

The meter has a standard RS485 communication port when the meter type is 

Acuvim-CL/DL/EL/KL.  The meter supports dual communication which means the 

RS485 serial communication can be used together withother RS-485 in extend 

module when the Acuvim-CL/DL/EL selected.
Serial communication terminals are A, B, S (14, 15, 16).  A is differential , B is 

differential signal – and S is shield.  Up to 32 devices can be connectedon a RS485 

bus.  The overall length of the bus cannot exceed 1200m (4000ft).  When multiple 

meters are connected serially on the same RS485 bus, each meter shall have a 

different device address.  Enter basic parameter setting page to set the device 

address.  This address can be any integer between 1 and 247.
Baud rate can be selected from one of the six values:  1200, 2400, 4800, 9600, 19200 

and 38400 bps. Parity needs to set one of the followings: Odd, Even, None1 (stop bit 1), 

None2 (stop bit 2).

I/O Options (if equipped)

Two types of IO modules with different IO combinations are available.
IO parameters can be set or viewed either from the meter front or through 

communication using utility software. Please refer to Acuvim-L user's manual for 

operation details.

Digital Input (DI)

DI is a dry point, no external power supply. DI can be used as pulse counter, to 

monitor switch status or to monitor sequence of events.

Summary of Contents for Acuvim-L Series

Page 1: ...Appearance and Dimension Installation Method Terminals Wiring Diagram Settings Mode Communication I O Options Time of Use DIN Rail Installation Specification Acuvim L Series Quick Setup Guide...

Page 2: ...00 3 583 35 90 10 00 0 394 14 00 0 551 35 90 91 00 3 583 38 00 1 496 7 60 0 300 1 413 1 413 50 70 1 996 Front View of the Display Meter and Remote Display Unit Gasket Side View of the Display Meter S...

Page 3: ...r Installation 35mm rail of the DIN rail Meter Voltage Input Terminals Used for voltage input Current Input Terminals Used for current input Power Supply Terminals Used for aux power supply input Comm...

Page 4: ...ical interference sources Meter s working temperature range is from 25 C to 70 C Meter can be installed into an ANSI C39 1 4 round or an IEC 92mm DIN square form Installation Steps 1 Meter Installatio...

Page 5: ...4 2 Remove installation clips from the meter and insert the meter into the square or round hole from the front side Gasket Gasket Panel Panel...

Page 6: ...ay meter and the remote display unit have the same installation method The DIN rail meter have a quite other installation method it must be installed on the 35mm rail You can references the others DIN...

Page 7: ...erminal strips Model Acuvim BL CL DL EL KL share the same strips When the Acuvim BL is selected the strips is used as DO When Acuvim CL DL EL KL would be selected the strips are used for communication...

Page 8: ...rminal and the switch gear s ground terminal together Auxiliary Power The meter has 2 auxiliary power supply options available for different applications aux power supply terminals are 11 12 13 1 Univ...

Page 9: ...he meter setting screen Press H to move the flashing cursor to the right press P to decrease the number by 1 once a time press E to increase the number by 1 once a time press V A to accept the change...

Page 10: ...ential signal B is differential signal and S is shield Up to 32 devices can be connectedon a RS485 bus The overall length of the bus cannot exceed 1200m 4000ft When multiple meters are connected seria...

Page 11: ...ront panel control keys the meter with DIN rail mount option includes the same functions as the panel mount version The default device address the default baud rate and the default check of the DIN ra...

Page 12: ...N wiring Installation Category III Pollution Degree 2 Metering Frequency 45 65Hz Overload 2times continuously 2500Vacpersecond norecurrence VoltagerangethroughPT 1000KV highest at primary side PT burd...

Reviews: