Acuvim-L Series : L-WEB User manual
www.accuenergy.com
V: 1.0 Revised: Sept. 2019
66
• Enter BACnet Port of the BBMD in "BBMD Port"
• Enter a value between 5-1440 min in the "Time To Live" for how often the foreign device will
register in the BBMD's foreign device table.
Click 'Save' after changing any settings. Users will be prompted to reboot the L-WEB immedi-
ately or later. If later is chosen the L-WEB must be rebooted from the 'Management' page in
order for the settings to take effect.
SNMP
The L-WEB module supports the Simple Network Management Protocol(SNMP) protocol for
reporting the metering data to the management station. The L-WEB uses a public community
string for read-only access. By default the module will communicate using SNMP port 161. The
L-WEB also supports 'traps' to send unsolicited messages to up to four management stations.
The settings for the SNMP protocol can be found by clicking on the 'Settings' tab and selecting
'Communications'. From the communications page select the 'SNMP' tab to access the settings
to configure the L-WEB for communication with a SNMP management station.
SNMP Enable: Select 'Enable' to enable the function and to further configure the settings
related to the SNMP protocol.
SNMP Port: By default the SNMP Port is configured to 161. The SNMP Port can be any value
from ranging from 16100 to 16199.
Read Only Community: By default the community string is Public, this configuration is similar
to a password which allows only authorized users to access the meters data.
Trap Enable: Select 'Enable' so that the meter will send a message to the management station
when an event is triggered. The event could be a change in Digital Input Status. The notifica-
tion can then be sent to up to 4 stations.