Acuvim-L Series : L-WEB User manual
www.accuenergy.com
V: 1.0 Revised: Sept. 2019
58
SFTP Enable: To download the logged data from the module using a FTP client, se-
lect Enable. The log file will then be available to be downloaded using a FTP client
using the following credentials:
Host: sftp://IPaddressofthemeter
Username: sftpuser
SFTP Password: accuenergy
Port: 22
By default the password for retrieving the backup log files is accuenergy. The user
can configure any password or can reset to the default of accuenergy by clicking on
the "Reset SFTP Password".
NOTE: After enabling the SFTP function the user must reboot the communication
module in order to access the data logs with the default password of 'accuenergy'.
Click 'Save' after changing any settings. Users will be prompted to reboot the L-WEB
immediately or later. If later is chosen the L-WEB must be rebooted from the 'Man-
agement' page in order for the changes to take effect.
Post Channel
The L-WEB supports the HTTP and FTP Post functions to send data from the meter
to a HTTP/FTP server. The L-WEB can post .csv files to three different HTTP or FTP
servers using HTTP Post or FTP Post.
In the case when there is no connection to the server, the L-WEB will store the posts
and send it out after the connection is restored. A maximum of 3000 files will be
buffered on module. The Clear Post Channel Logs button will allow users to clear
the buffered files on meter.
The L-WEB can post data to a server at intervals of time ranging from 1 minute to 1
month.
The settings for configuring the post channels to post the data can be found by
clicking on 'Settings' and then selecting 'Communications' tab. Click "Post Chan-
nels" to configure any of the three post channels.