CT2 Value
word
R/W
1; 5; 100; 200; 333
According
to the
order
1~4
1
213H
531
CT1 Value
word
R/W
1~50000/5~50000
5
1~4
1
214H
532
CTN Value
word
R/W
1~50000/5~50000
5
4
1
215H
533
PT2 Value
word
R/W
50.0~400.0
(Communication value
is 10 times of the real
value)
220.0
1~4
1
216H-
217H
534-
535
PT1 Value
word
R/W
50.0~999999.9
(Communication value
is 10 times of the real
value)
220.0
1~4
2
218H
536
Energy Pulse
Constant
word
R/W
1-60000
5000
1~4
1
219H
537
Energy Pulse
Width
word
R/W
20-100 ms
80
1~4
1
21AH
538
Energy display
Decimal
word
R/W
0,1, 2, 3
1
1~4
1
21BH
539
Relay Operating
Mode
word
R/W
0: Relay Control
1: Alarm Output
0
2~4
1
21CH
540
connection
detection enable word
R/W
0:No enable 1:Enable
1
1~4
1
Table 5-14 display programming table
Page
No.
Setting flag
Content
Model
1
Model
2
Model
3
Model
4
1
Voltage wiring detection
√
√
√
√
2
Current connection
detection
√
√
√
√
3
Instrument address
√
√
√
√
4
RS485 communication baud
rate
√
√
√