22
13
TECHNICAL
DATA
13.1
OUTDOOR
UNITS
TECHNICAL
DATA
Power
supply
230V/1/50Hz
230V/1/50Hz
230V/1/50Hz
400V/3/50Hz
Max.
power
input
kW
2.81
3.80
5.47
6.15
Max.
starting
current
A
7.9
10.0
15.6
8.7
Electrical
data
Max.
current
input
A
12.6
17.1
24.5
14.6
Brand
SANYO
HITACHI
MITSUBISHI
SIAM
MITSUBISHI
SIAM
Model
C
‐
6RVN93H0V
ATL165SD
‐
C9AU
TNB306FPGM
ANB42FBEMT
Type
Rotary
DC
Inverter
Rotary
DC
Inverter
Twin
Rotary
DC
inverter
Scroll
DC
inverter
Number
1
1
1
1
Power
input
in
cooling
mode
(1)
kW
1.31
1.73
2.43
3.00
Power
input
in
cooling
mode
(2)
kW
1.40
1.90
2.65
3.21
Power
input
in
heating
mode
(3)
kW
1.49
2.07
3.25
3.92
Power
input
in
heating
mode
(4)
kW
1.23
1.72
2.58
3.15
Compressor
Refrigerant
oil
(type,
quantity)
mL
FV
50S,
350
68HES
‐
H,
880
FV50S,
870
MEL
56,
1700
Model
YDK53
‐
6Y
YDK53
‐
6Z
YDK100
‐
6A
YDK100
‐
6A
Type
AC
motor
AC
motor
AC
motor
AC
motor
Number
1
1
2
2
Rated
power
input
kW
0.13
0.15
0.19
(×2)
0.19
(×2)
Rated
running
current
A
0.59
0.69
0.87
(×2)
0.87
(×2)
Condensator
uF
3uF/450VAC
3uF/450VAC
3uF/450VAC
3uF/450VAC
Speed
r/min
770
815
860
860
Fan
motor
Max.
air
flow
m
3
/s
0.71
0.89
1.65
1.67
Number
of
rows
1.6
2
2.6
2
Tube
pitch
×
row
pitch
mm
22×19.05
25.4×22
25.4×22
25.4×22
Fin
gap
mm
1.4
1.5
1.5
1.8
Fin
type
Hydrophilic
aluminiun
Hydrophilic
aluminium
Hydrophilic
aluminium
Hydrophilic
aluminium
Tube
outside
diameter
and
type
mm
Ф
7.94
Innergroove
copper
tube
Ф
9.53
Innergroove
copper
tube
Ф
9.53
Innergroove
cooper
tube
Ф
9.53
Inner
groove
copper
tube
Length
×
height
×
depth
(condenser)
mm
778×660×38.1
758×813×44
887×1220×44
887×1220×44
Condenser
Number
of
circuits
2
2
8
8
Type
R410A
R410A
R410A
R410A
Refrigerant
charge
(5)
kg
1.60
1.80
3.30
4.20
Refrigerant
Pressure
design
(high/low)
MPa
4.2/2.0
4.2/2.0
4.2/2.0
4.2/2.0
Liquid
side
/
Gas
side
mm
6.4/12.7
9.5/15.9
9.5/15.9
9.5/15.9
Max.
Refrigerant
pipe
length
m
25
25
30
30
Max.
difference
in
level
(out.
unit
is
up)
m
12
12
20
20
Refrigerant
piping
Max.
difference
in
level
(out.
unit
is
down
m
9
9
12
12
Sound
pressure
(6)
dB(A)
38÷58
40÷59
41÷61
41÷62
Noise
Sound
pressure
(7)
dB(A)
46÷67
48÷68
49÷70
49÷71
Dimensions
(L×A×P)
mm
842×695×324
895×862×313
940×1245×360
940×1245×360
Packing
(L×A×P)
mm
965x752x399
1043×915×395
1080×1285×435
1080×1285×435
Dimensions
and
weight
Net/Gross
weight
kg
59/63
73/76
106/114
115/121
Operating
conditions:
(1)
Cooling:
Outdoor
air
temperature
35°C;
inlet/outlet
water
temperature
12/7°C.
(2)
Cooling:
Outdoor
air
temperature
35°C;
inlet/outlet
water
temperature
23/18°C.
(3)
Heating:
Outdoor
air
temperature
7°C
DB
6°C
WB;
inlet/outlet
water
temperature
40/45°C.
(4)
Heating:
Outdoor
air
temperature
7°C
DB
6°C
WB;
inlet/outlet
temperature
30/35°C.
(5)
Refrigerant
charge
valide
until
5m
of
distance
between
indoor
and
outdoor
units.
Above
5m,
add
20g/m
of
refrigerant
for
the
model
i
‐
SHWAK/WP
07
and
50g/m
of
refrigerant
for
the
models
i
‐
SHWAK/WP
09
‐
12
‐
16.
(6)
Sound
pressure
level
measured
at
1m
from
the
unit,
in
free
field,
according
to
ISO
3746.
(7)
Sound
pressure
levels
are
measured
in
free
field
environment
at
1m
and
1.5m
above
the
ground,
according
to
DIN
45635.
N.B.
The
performance
data
shown
is
indicative
and
could
be
subject
to
change.
PACK DUE 7
PACK DUE 9
PACK DUE
12
PACK DUE 16
Summary of Contents for PACK DUE 7
Page 1: ......
Page 39: ...38 22 2 OUTDOOR UNITS 22 2 1 Wiring diagram of PACK DUE 9...
Page 40: ...39 22 2 2 Wiring diagram of PACK DUE 12...
Page 41: ...40 22 2 3 Wiring diagram of PACK DUE 16...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......