23
13.2
INDOOR
UNITS
TECHNICAL
DATA
Units
Power
supply
230V/1/50Hz
230V/1/50Hz
230V/1/50Hz
230V/1/50Hz
Max.
Power
input
kW
3.13
3.13
4.13
4.13
Electrical
data
Max.
input
current
A
13.68
13.68
17.98
17.98
Cooling
capacity
(1)
kW
4.71
6.09
9.03
10.82
Input
power
(1)
kW
1.52
1.96
2.90
3.49
E.E.R.
(1)
W/W
3.10
3.11
3.11
3.10
Cooling
capacity
(2)
kW
6.12
8.12
11.90
14.07
Input
power
(2)
kW
1.61
2.13
3.12
3.70
Cooling
E.E.R.
(2)
W/W
3.80
3.81
3.82
3.80
Heating
capacity
(3)
kW
5.44
7.44
11.98
14.10
Input
power
(3)
kW
1.70
2.32
3.72
4.35
C.O.P.
(3)
W/W
3.20
3.21
3.22
3.24
Heating
capacity
(4)
kW
5.90
8.01
12.58
14.95
Power
consumption
(4)
kW
1.44
1.95
3.05
3.64
Heating
C.O.P.
(4)
W/W
4.10
4.11
4.12
4.10
Water
flow
(4)
L/s
0.28
0.38
0.60
0.71
Head
pressure
(4)
kPa
48
45
38
32
Max.
input
power
of
water
pump
kW
0.13
0.13
0.13
0.13
Max.
input
current
of
water
pump
A
0.58
0.58
0.58
0.58
Expansion
vessel
L
10
10
10
10
Hydraulic
connections
inch
1”M
1”M
1”M
1”M
Minimum
valume
of
water
L
10
10
16
20
Hydraulic
circuit
Maximum
volume
of
water
L
350
350
350
350
Liquid
side
connection
inch
1/4”
SAE
3/8”
SAE
3/8”
SAE
3/8”
SAE
Refrigerant
circuit
Gas
side
connection
inch
1/2”
SAE
5/8”
SAE
5/8”
SAE
5/8”
SAE
Power
input
kW
3.0
3.0
4.0
4.0
Integrative
resistance
Current
input
A
13.10
13.10
17.40
17.40
Dimensions
(L×A×P)
mm
515×816×270
515×816×270
515×816×270
515×816×270
Net
weight
kg
30
32
34
34
Dimensions
and
weight
Gross
weight
kg
33
35
37
37
Operating
conditions:
(1)
Cooling:
Outdoor
air
temperatue
35°C;
inlet/outlet
temperature
12/7°C.
(2)
Cooling:
Outdoor
air
temperature
35°C;
inlet/outlet
temperature
23/18°C.
(3)
Heating:
Outdoor
air
temperature
7°C
DB
6°C
WB.;
temp.acqua
ing./usc.
40/45°C.
(4)
Heating:
Outdoor
air
temperature
7°C
DB
6°C
WB;
inlet/outlet
temperature
30/35°C.
N.B.
‐
The
performance
data
are
indicative
and
could
be
subject
to
change.
‐
The
electrical
data
are
shown
to
scale
the
size
of
the
circuit
breakers
and
power
cables
for
the
indoor
unit.
14
ELECTRIC
DATA
Power
supply
of
the
unit
V/~/Hz
230/1/50*
‐
400/3/50**
Remote
control
circuit
V/~/Hz
12
/
1
/
50
Control
board
circuit
V/~/Hz
12
/
1
/
50
Fans
power
supply
V/~/Hz
230
/
1
/
50
Note:
Electric
data
may
change
for
updating
the
manual.
It
is
therefore
necessary
to
refer
always
to
the
wiring
diagram
of
this
manual
supplied
with
the
unit.
PACK DUE
7
PACK DUE
9
PACK DUE
12
PACK DUE
16
*
For
all
indoor
units
and
outdoor
units
PACK DUE
7,
PACK DUE
9,
PACK DUE
12.
**
For
the
model
PACK DUE
16.
Summary of Contents for PACK DUE 7
Page 1: ......
Page 39: ...38 22 2 OUTDOOR UNITS 22 2 1 Wiring diagram of PACK DUE 9...
Page 40: ...39 22 2 2 Wiring diagram of PACK DUE 12...
Page 41: ...40 22 2 3 Wiring diagram of PACK DUE 16...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......