SM01P
20
11.3 Three-Wire Start/Stop Control
Momentary
STOP
Contact
1
2
25
13A
13E
13B
STOP
5
6
11
16
17
SIGNAL COMMON
0-10V DC INPUT
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13E FUNCTION SELECT
4-20mA INPUT
FORM A RELAY
-
+
+
SPEED POT POWER SUPPLY
DIGITAL INPUT REFERENCE
Momentary
START
Contact
(START REVERSE)
REV
FWD
(START FORWARD)
3-Wire Start/Stop Control
NOTE
•
Program TB-13E (Parameter 12) for START FORWARD (06) .
•
If reverse direction is required, set ROTATION (Parameter 17) to FORWARD
AND REVERSE (02), and program TB-13A (Parameter 10) for START
REVERSE (07) .
•
Momentarily close TB-13E to TB-11 to START in the forward direction, or close
TB-13A to TB-11 to START in the reverse direction . Momentarily open TB-1 to
TB-11 to STOP the drive .
•
For 0-10 VDC or 4-20 mA speed control, set STANDARD SPEED SOURCE
(Parameter 05) to 0-10 VDC (03) or 4-20 mA (04) .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]