SM01P
12
7.3
Input Wire Size Requirements
INPUT WIRE SIZE REQUIREMENTS
120 Vac 1 phase
208/240 Vac 1 phase
208/240 Vac 3 phase
400/480 Vac 3 phase
MODEL AWG mm
2
MODEL AWG mm
2
MODEL AWG mm
2
MODEL AWG mm
2
SM004S
14
2.5
S_204S
14
2.5
SM005S
14
2.5
S_205S
14
2.5
SM205
14
2.5
SM405
14
2.5
S_208S
14
2.5
SM010S
12
4.0
S_210S
14
2.5
SM210
14
2.5
SM410
14
2.5
SM015S
10
6.0
S_215S
14
2.5
SM215
14
2.5
SM415
14
2.5
S_220S
12
4.0
SM220
14
2.5
SM420
14
2.5
S_230S
10
6.0
SM230
14
2.5
SM430
14
2.5
SM250
12
4.0
SM450
14
2.5
SM275
8
10
SM475
12
4.0
SM2100
8
10
SM4100 10
6.0
SM2150
6
16
SM4150
8
10
7.4
Installation According to EMC Requirements
The SCM and SCL Series can be installed to meet the European standards for
Electromagnetic Compatibility (EMC) requirements . These requirements govern the
permissible electromagnetic emissions and immunity, both radiated and conducted, of
a drive system .
The EMC requirements apply to the final installation in its entirety, not to the individual
components used . Because every installation is different, the recommended installation
should follow these guidelines as a minimum . Additional equipment (such as ferrite core
absorbers on power conductors) or alternative wiring practices may be required to meet
conformance in some installations .
Filter:
The input to the drive (or group of drives) must include a filter to reduce the electrical
noise reflected back to the AC Line . The SCL Series includes a filter that has been tested
to meet the industrial standards set by the EU, EN 61800-3 for conducted emissions and
EN 55011 for radiated emissions to class A compliance when installed in a control cabinet
with a motor cable < 10m . The SCM can be installed to meet these same standards when
used with an appropriately installed external line filter .
EMC
Compliance with EN 61800-3/A11
Installation:
Shielded cable must be used for all control and power cables
and exposed wiring must be kept as short as possible .
A
Screen clamps
B
Control cable
C
Low-capacitance motor cable
(core/core < 75 pF/m, core/screen < 150 pF/m)
D
Electrically conductive mounting plate
E
Filter
SM01 1
B
C
D
A
E
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]