ABNOX Temperature Controller AXTR-xxxxxx-xxxxx
Page 76 of 84
Outputs (OutL, OutA)
The configuration of the device outputs is divided into binary outlets (OutL) and analog outlets (OutA). Switch-
ing statuses of the binary outlets 1 to 3 (5) will be indicated by the LEDs K1 to K3 (K5) (LED on = outlet ac-
tive).
Binary Outputs
As a standard, the device comes with a relay output (make contact; output 1); optionally, it can be equipped
with two (four) additional binary outlets (relay or logic output; outlets 2 to 5).
ConF
-
>
OutL
-
>
Parameter
Value
Description
Output 1 ... 5
Out1
Out2
Out3
Out4
Out5
0
Output not active
(factory set for Out2 ... Out5)
1
Controller output 1
(factory set at Out1)
2
Controller output 2
3
Binary input
4
Limit value monitoring 1
5
Limit value monitoring 2
6
Timer signal
(Setup program: the output signal can be inverted.)
Analog Output
Optionally, the device can be equipped with an analog output (outlet 2).
ConF
-
>
OutA
-
>
Parameter
Value
Description
Function
FnCt
9
Function of output;
9 = controller outlet 1
Type of signal
SiGn
Physical output signal
0
0 ... 20 [mA]
1
4 ... 20 [mA]
2
0 ... 10 [V]
Value for Out-of-Range
rOut
0
... 101
Signal (as percentage) for exceeding or falling short of
measuring range 101 = last output signal
Zero point
0Pnt
-1999 ...
0
... +9999
Value range of the basic value for the physical output sig-
nal
Final value
End
-1999
...
100
...
+9999